Plan Review Notes
Plan Review Notes For Permit 16030359
Permit Number 16030359
Review Stop B
Sequence Number 1
Notes
Date Text
2016-03-09 10:03:11FLORIDA BUILDING CODE, 2014 5TH EDITION
  
 1) REVIEWED THE ATTACHED ENGINEERING LETTER REFERENCING
 THE CONSTRUCTION OF THE OVERHEAD PROTECTION SCAFFOLDING
 AND BARRICADES PROVIDED AT THE NORTH (FRONT) ELEVATION
 OF THE BUILDING.
  
 2) PROVISOS: A) PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS/ENGINEERING FOR THE SCAFFOLDING
 ASSEMBLY: FBC, SECTION 3306.7.
  
 B) PLEASE SUBMIT A LIFE SAFETY PLAN/EVACUATION PLAN:
 INDICATE MEANS OF INGRESS/EGRESS(EXIT ACCESS,EXIT AND
 EXIT DISCHARGE), AND OCCUPANCY LOAD FROM THE BUILDING
 THRU THE SCAFFOLDING SYSTEM. FBC, SECTION 1001.4. THE
 MEANS OF EGRESS CONTINUITY SHALL BE MAINTAINED AT ALL
 TIMES PURSUANT TO THE FBC, SECTION 1001.3.
  
 C) ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL TIMES
 PURSUANT TO THE FBC, SECTION 3306.7 AND REQUIRES A
 PERMIT PER FBC, SECTION 105.1.
  
 D) NEED ENGINEERING CALCULATIONS, SPECIFICATIONS, AND
 DETAILS REFERENCING THE EXTERIOR BRICK VENEER
 MITIGATION PROCEDURES.
  
 E) REQUIRE A "MAINTENANCE OF TRAFFIC" PERMIT FROM OUR
 ENGINEERING DEPARTMENT.
  
  
  
  
  