| Date |
Text |
| 2016-11-28 14:45:28 | RESIDENTIAL (R3) ADDITION/ALTERATION SIXTH BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | NOTE: |
| | THE PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY |
| | CALCULATIONS. |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION |
| | |
| | |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM, INCLUDING CORRECT OWNER'S NAME, BUILDER NAME, |
| | PERMIT OFFICE AND JURISDICTION NUMBER. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NEEDS BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION NUMBER. |
| | |
| | B) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014) |
| | REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC |
| | INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| | VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE |
| | EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION |
| | RATIO. OTHERWISE REVISE AS REQUIRED. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. SEE ARCHITECTURAL |
| | PLANS. THEY CALL FOR 1/150 RATIO NOT 1/300. REVISE AS |
| | REQUIRED. |
| | |
| | C) COMPLETE THE INSPECTION CHECKLIST AS REQUIRED BY |
| | SEC. R405.4.2 FBC-ENERGY CONSERVATION. |
| | RESPONSE: |
| | INSPECTION CHECKLIST NEED TO BE COMPLETED. CHECKLIST |
| | NEED TO BE CHECKED WITH THE ITEMS THAT APPLY. |
| | |
| | D) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE |
| | ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2 |
| | FBC-ENERGY CONSERVATION. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED AT ALL. THE NAME OF THE |
| | PERSON COMPLETING THE ENERGY CALCULATIONS WAS NOT |
| | PROVIDED. ONLY A COPY OF A SIGNATURE WAS PROVIDED. |
| | PROVIDE THE COMPLETE NAME OF THE PERSON COMPLETING THE |
| | CALCULATIONS. |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC |
| | FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE |
| | REQUIRED FOR VERIFICATION. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |