| 2016-08-09 17:47:44 | |
| | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. PERMIT CAN NOT BE ISSUED |
| | WITHOUT THE ENERGY CALCULATIONS. SEC. R103.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 2- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET |
| | A-7 DON'T MATCH DESIGN PRESSURES SPECIFIED ON SHEET |
| | A-2. REVISE AS REQUIRED. SEC. R301 OF FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). |
| | RESPONSE: |
| | THE DESIGN PRESSURES WERE DELETED FROM SHEET A-2. THOSE |
| | DESIGN PRESSURES WERE CORRECT. THEY CORRESPONDED TO |
| | EXPOSURE "C". THE DESIGN PRESSURES SHOWN ON SHEET A-7 |
| | DON'T CORRESPOND TO EXPOSURE "C". ALSO, THE DESIGN |
| | PRESSURES ON THE SMALL OPENINGS CAN NOT BE LOWER THAN |
| | THE BIGGER OPENINGS. THE SMALLER THE TRIBUTARY AREA, |
| | THE HIGHER THE DESIGN PRESSURES. REVISE ALL THE DESIGN |
| | PRESSURES SHOWN ON SHEET A-7. NOTE: MAKE SURE DESIGN |
| | PRESSURES ARE GIVEN BASED ON THE OPENING SIZE AND |
| | DISTANCE FROM THE EDGE OF BUILDING. FIGURE R301.2(7) |
| | REQUIRES 4'-0" MINIMUM AS THE EDGE DISTANCE FOR ALL |
| | CASES. |
| | |
| | ORIGINAL COMMENT: |
| | 3- PROVIDE COMPLETE WALL SECTION THRU GABLE END SHOWING |
| | COMPLIANCE WITH SEC. R609.4 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | RESPONSE: |
| | RESPONSE LETTER STATED THAT "MASONRY WALL IS EXISTING". |
| | THIS IS NOT CORRECT. THE WEST GABLE END WALL BY THE |
| | KITCHEN AREA IS NEW. THE "PERSPECTIVE OF GABLE END |
| | TRUSS" DETAIL SHOWN ON SHEET A-6 DOESN'T MATCH TRUSS |
| | PLAN SHOWN ON SAME SHEET. THERE IS NO GABLE END TRUSS. |
| | THERE ARE NOT CONNECTORS SPECIFIED FOR THE 2X4 |
| | OUTRIGGERS. THERE ARE NOT GABLE END VERTICAL WEBS |
| | LARGER THAN 4'-0". THEREFORE THE VERTICAL REINFORCEMENT |
| | WOULDN'T APPLY. SEC. R609.4 OF FBC-RESIDENTIAL REQUIRES |
| | CONCRETE BLOCK WALL TO BE CONTINUOUS TO THE ROOF LINE. |
| | OTHERWISE, WOOD FRAME CONSTRUCTION REQUIRES CONFORMANCE |
| | WITH TABLES R609.4A AND R609.4B AND FIGURE R609.4. SEE |
| | EXCEPTION FOR SEC. R609.4. PROVIDE A COMPLETE |
| | SECTION/DETAIL SHOWING HOW PROVIDING A CONTINUOUS LOAD |
| | PATH FROM THE ROOF TO THE CONCRETE BLOCK WALL. SPECIFY |
| | ALL CONNECTORS AS REQUIRED BY SEC. R801.2 |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FIXED WINDOWS AS SHOWN ON PLANS. NONE SUBMITTED AT |
| | THIS TIME. |
| | |
| | ORIGINAL COMMENT: |
| | B) INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | RESPONSE: |
| | THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED. |
| | NONE OF THEM MATCH SINGLE INSWING DOOR TYPE AS SHOWN ON |
| | PLANS. BOTH PRODUCT APPROVALS ARE FOR DOUBLE DOORS OR |
| | SINGLE DOOR WITH SIDELITE. NOT SINGLE DOORS ONLY. |
| | PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS AND DOOR |
| | SCHEDULE. |
| | |
| | NOTE: DOOR SCHEDULE ON SHEET A-8 DOESN'T MATCH |
| | INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED TO |
| | MATCH. |
| | |
| | ORIGINAL COMMENT: |
| | C) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT |
| | GLASS. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | |
| | RESPONSE: |
| | FRENCH DOORS FLORIDA PRODUCT APPROVAL FL16904-R3 |
| | SUBMITTED IS FOR NON-IMPACT DOORS. NEED TO PROVIDE |
| | SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION |
| | SCHEDULE. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | NEW COMMENT: |
| | 6- SITE PLAN FOOTPRINT SUBMITTED DOESN'T MATCH PROPOSED |
| | FLOOR PLAN ON SHEET A-5. REVISE AS REQUIRED TO MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T |
| | STAPLE OLD DRAWINGS. |
| | |