| Plan Review Notes For Permit 16030347 |
| Permit Number |
16030347 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-12 05:17:23 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. UPDATE ALL APPLICABLE CODES ON GENERAL NOTES TO | | | REFLECT NEW FBC 2014 5TH EDITION SET AND NFPA 70 NEC | | | 2011. | | | 2. PROVIDE AIC CALCULATIONS FOR NEW SERVICE PER FBC RES | | | E3606 | | | 3. PROVIDE A NOTE TO INDICATE THE REQUIREMENTS OF FBC | | | RES 404.1- 75% OF LAMPS TO BE HIGH EFFICACY LAMPS. | | | 4. SHOW ON PANEL SCHEDULE THE CONDUCTOR SIZE FOR THE | | | WATER HEATER. NEC 310.15B16 | | | 5. PER FBC RES E3706, SHOW AND LABEL BRANCH CIRCUITS ON | | | PANEL BOARDS SPECIFIC AREA AS TO WHAT IT SERVES. | | | GENERAL LIGHTING DESIGNATION WILL NOT SUFFICE. MUST BE | | | CLEAR AND EVIDENT AS TO WHAT IT ENERGIZES. | | | 6. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|