| 2016-09-02 13:15:13 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. CONSTRUCTION DOCUMENTS TO BE SIGNED BY DESIGNER. |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE |
| | REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15 |
| | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA |
| | STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE |
| | SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS |
| | TO BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 2. SHT. M-1.1 PLEASE CLARIFY NOTE ON RISER AT KIT 3IN |
| | PVC TO EXIST W/C SHOULD IT BE TO EXISTING SEWER OR |
| | BUILDING DRAIN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3 SHOW TRAPS AT FIXTURES. WPB AMEND TO FBC 107.2.1 |
| | SHALL COMPLY WITH FBC PL 1002.1 |
| | |
| | 4. OVERFLOW ON TUB CAN NOT BE USED AS A VENT MOST |
| | BATHROOM GROUPS ARE VENTED BY THE VENT ON THE LAVATORY |
| | SHALL COMPLY WITH FBC PL |
| | 912.1 HORIZONTAL WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE |
| | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE |
| | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND |
| | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION |
| | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM |
| | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH |
| | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT |
| | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT. |
| | |
| | |
| | |