2016-04-04 12:00:422ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030299
 4/4/16
  
 1) SHEET M100: HVAC NOTE INDICATES "DS DETECTORS TO BE
 INSTALLED IN ALL RETURN DUCTS", HOWEVER THE PLANS SHOW
 DS SYMBOLS AT THE SUPPLY DUCTS OF THE SYSTEMS. PLEASE
 NOTE THAT THE CODE IS A MINIMUM COMPLIANCE PATH AND
 WHERE DS DETECTORS ARE REQUIRED PER SECTION 606.2.1,
 THEY SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS.
 2) PLEASE PROVIDE A HEAT REJECTION CALCULATION TO
 CLARIFY HOW AC -2A WAS SIZED. THE SCHEDULE INDICATES A
 3-TON SYSTEM FOR THE IT ROOM WHICH IS APPROXIMATELY 60
 SQ.FT.
 3) PROVIDE THE MIAMI-DADE NOA FOR THE ALUMA-STAND
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR.
 4) THE SUBMITTED SPECIFICATIONS FOR THE XVENT BOX DO
 NOT INDICATE THE PRODUCT HAS BEEN TESTED AND CETRTIFIED
 TO MEET THE AMCA 550 STANDARD FOR AIR PERFORMANCE,
 WATER PENETRATION, AND WIND-DRIVEN RAIN- SEE SECTIONS
 401.5 AND 501.3.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER