Plan Review Notes
Plan Review Notes For Permit 16030299
Permit Number 16030299
Review Stop P
Sequence Number 1
Notes
Date Text
2016-03-16 13:28:331ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE LETTER FROM ARCHITECT REQUESTING RELIEF FOR
 HOT WATER REQUIRED ON THE TUB AND SHOWERS PER FBC PL
 SEC. 607.1
 2. BACK FLOW REQUIRED ON AUTOFILL FOR FOUNTAIN. PER FBC
 PL SEC. 608.13
 3. PROVIDE MANUFACTURE SPEC SHEETS FOR STEAM
 UNIT,BOOSTER PUMP AND WATER HEATERS. PER WPB AMEND. TO
 FBC SEC. 107.2.1
 4. SHOW LOCATION OF OF WATER HEATER PAN DRAIN SHT.P100.
 PER WPB AMEND.TO FBC SEC. 107.2.1
 5. SHT. P100 SHOWS STORAGE TANK WATER HEATER SHT. P300
 DETAILED ELELECTRIC WATER HEATER SHOWS TANKLESS PLEASE
 CLARIFY. PER WPB AMEND.TO FBC SEC. 107.2.