2016-03-15 08:07:151ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION
 PERMIT #16030299
 3/15/16
  
 1) REFER TO SECTION C403.2.7.6 FBC-14 ENERGY
 CONSERVATION: AIR-HANDLING UNITS SHALL NOT BE ALLOWED
 IN ATTICS OF COMMERCIAL BUILDINGS. SHEET A100 SHOWS
 AHU'S 1, 3, 4, 5, 6, 7 IN THE ATTIC SPACE- PLEASE
 CORRECT THE PLANS AND DETAILS.
 2) THE SUBMITTED ENERGY FORM C402-2014 DOES NOT SHOW
 COMPLIANCE DATA FOR THE NEW MINI-SPLIT AC SYSTEMS.
 3) THE AC CALCULATIONS INDICATE 8.63 TONS FOR AHU-1 AND
 4.26 TONS FOR AHU-3, HOWEVER THE EXISTING SYSTEMS SHOWN
 ON M300 INDICATE 6.5 TON FOR AHU-1, AND 2.5 TON FOR
 AHU-3. IT WOULD APPEAR THE TWO EXISTING SYSTEMS ARE
 UNDERSIZED.
 4) SHEET M100: ACCESS PANELS ARE REQUIRED FOR THE
 ABOVE-CEILING AIR HANDLERS. REFER TO SECTION 306.1 AND
 PROVIDE A DIMENSIONED DETAIL FOR CONSTRUCTION AND
 INSTALLATION OF THE PANELS.
 5) M100: A DUCT SMOKE DETECTOR SHALL BE INSTALLED IN
 THE RETURN AIR SYSTEMS OF AHU-1- SECTION 606.2.1 FBC-14
 MECHANICAL. PLEASE INDICATE HOW ALL OF THE DS DETECTORS
 WILL BE SUPERVISED IN COMPLIANCE WITH 606.4.1.
 6) M100: SHOW THE LOCATIONS OF CU'S 1A, 2A, & # 3A, AND
 PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION- SECTION
 301.15.
 7) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS
 AND SPACES OF THE NEW OCCUPANCY- SEE TABLE 403.3 FBC-14
 MECHANICAL AND PROVIDE A SCHEDULE ON THE PLANS
 INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR
 AIR.
 8) PLEASE CORRECT THE NOTE BY THE OUTDOOR AIR INTAKE
 FOR AHU'S 2 & 3: A MOTORIZED OR GRAVITY DAMPER IS
 REQUIRED FOR THE INTAKE PER SECTIONS C402.4.5 AND
 C402.4.5.2 FBC-14 ENERGY CONSERVATION. PLEASE SEE
 SECTION 401.4 FBC-14 MECHANICAL AND SHOW REQUIRED
 CLEARANCES FOR ALL AIR INTAKES.
 9) INDICATE HOW THE EXHAUST AND AIR INTAKE OPENINGS
 WILL BE PROTECTED FROM WIND BORNE DEBRIS- SEE CHAPTER
 19 FBC BUILDING. PLEASE NOTE THAT ALL SUBMITTALS (
 MANUFACTURER'S SPECIFICATIONS, PRODUCT APPROVALS, NOA'S
 ETC.) SHALL BE REVIEWED AND APPPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  