| 2016-03-15 08:07:15 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION |
| | PERMIT #16030299 |
| | 3/15/16 |
| | |
| | 1) REFER TO SECTION C403.2.7.6 FBC-14 ENERGY |
| | CONSERVATION: AIR-HANDLING UNITS SHALL NOT BE ALLOWED |
| | IN ATTICS OF COMMERCIAL BUILDINGS. SHEET A100 SHOWS |
| | AHU'S 1, 3, 4, 5, 6, 7 IN THE ATTIC SPACE- PLEASE |
| | CORRECT THE PLANS AND DETAILS. |
| | 2) THE SUBMITTED ENERGY FORM C402-2014 DOES NOT SHOW |
| | COMPLIANCE DATA FOR THE NEW MINI-SPLIT AC SYSTEMS. |
| | 3) THE AC CALCULATIONS INDICATE 8.63 TONS FOR AHU-1 AND |
| | 4.26 TONS FOR AHU-3, HOWEVER THE EXISTING SYSTEMS SHOWN |
| | ON M300 INDICATE 6.5 TON FOR AHU-1, AND 2.5 TON FOR |
| | AHU-3. IT WOULD APPEAR THE TWO EXISTING SYSTEMS ARE |
| | UNDERSIZED. |
| | 4) SHEET M100: ACCESS PANELS ARE REQUIRED FOR THE |
| | ABOVE-CEILING AIR HANDLERS. REFER TO SECTION 306.1 AND |
| | PROVIDE A DIMENSIONED DETAIL FOR CONSTRUCTION AND |
| | INSTALLATION OF THE PANELS. |
| | 5) M100: A DUCT SMOKE DETECTOR SHALL BE INSTALLED IN |
| | THE RETURN AIR SYSTEMS OF AHU-1- SECTION 606.2.1 FBC-14 |
| | MECHANICAL. PLEASE INDICATE HOW ALL OF THE DS DETECTORS |
| | WILL BE SUPERVISED IN COMPLIANCE WITH 606.4.1. |
| | 6) M100: SHOW THE LOCATIONS OF CU'S 1A, 2A, & # 3A, AND |
| | PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION- SECTION |
| | 301.15. |
| | 7) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND |
| | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS |
| | AND SPACES OF THE NEW OCCUPANCY- SEE TABLE 403.3 FBC-14 |
| | MECHANICAL AND PROVIDE A SCHEDULE ON THE PLANS |
| | INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR |
| | AIR. |
| | 8) PLEASE CORRECT THE NOTE BY THE OUTDOOR AIR INTAKE |
| | FOR AHU'S 2 & 3: A MOTORIZED OR GRAVITY DAMPER IS |
| | REQUIRED FOR THE INTAKE PER SECTIONS C402.4.5 AND |
| | C402.4.5.2 FBC-14 ENERGY CONSERVATION. PLEASE SEE |
| | SECTION 401.4 FBC-14 MECHANICAL AND SHOW REQUIRED |
| | CLEARANCES FOR ALL AIR INTAKES. |
| | 9) INDICATE HOW THE EXHAUST AND AIR INTAKE OPENINGS |
| | WILL BE PROTECTED FROM WIND BORNE DEBRIS- SEE CHAPTER |
| | 19 FBC BUILDING. PLEASE NOTE THAT ALL SUBMITTALS ( |
| | MANUFACTURER'S SPECIFICATIONS, PRODUCT APPROVALS, NOA'S |
| | ETC.) SHALL BE REVIEWED AND APPPROVED BY THE DESIGN |
| | PROFESSIONAL OF RECORD. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |