| 2016-03-14 17:33:19 | JOB PERMIT NUMBER: 16030299 |
| | JOB ADDRESS: 820 S DIXIE HIGHWAY |
| | WEST PALM BEACH FLORIDA |
| | DATE: MARCH 14 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY |
| | - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| | - NEC 240.24 E OVERCURRENT DEVICES OTHER THAN |
| | SUPPLEMENTARY OCPD SHALL NOT BE LOCATED IN BATHROOMS |
| | PLEASE RELOCATE PANELS. KEEP NEC 110.26 WORKING SPACE |
| | CLEARANCE IN MIND FOR POSITIONING. PLEASE CLARIFY ? |
| | - NEC 210.8 B GFCI PROTECTION REQUIRED FOR RECEPTACLES |
| | INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF SINKS. |
| | - NEC 110.9 , 110.10 PROVIDE AIC CALCULATIONS FROM FPL |
| | TRANSFORMER TO MAIN DISCONNECT AND FROM DISCONNECT TO |
| | EACH INDIVIDUAL PANEL ? |
| | - NEC 110.16 , 110.24 PROVIDE ARC-FLASH HAZARD WARNING |
| | LABEL AND AVAILABLE FAULT CURRENT MARKINGS. |
| | - MUST COMPLY WITH FBC-E SECTION 405 MANDATORY LIGHTING |
| | CONTROLS A NOTE WILL SUFFICE. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |