Plan Review Notes
Plan Review Notes For Permit 16030299
Permit Number 16030299
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-14 17:33:19JOB PERMIT NUMBER: 16030299
 JOB ADDRESS: 820 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: MARCH 14 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY
 - NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 - NEC 240.24 E OVERCURRENT DEVICES OTHER THAN
 SUPPLEMENTARY OCPD SHALL NOT BE LOCATED IN BATHROOMS
 PLEASE RELOCATE PANELS. KEEP NEC 110.26 WORKING SPACE
 CLEARANCE IN MIND FOR POSITIONING. PLEASE CLARIFY ?
 - NEC 210.8 B GFCI PROTECTION REQUIRED FOR RECEPTACLES
 INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF SINKS.
 - NEC 110.9 , 110.10 PROVIDE AIC CALCULATIONS FROM FPL
 TRANSFORMER TO MAIN DISCONNECT AND FROM DISCONNECT TO
 EACH INDIVIDUAL PANEL ?
 - NEC 110.16 , 110.24 PROVIDE ARC-FLASH HAZARD WARNING
 LABEL AND AVAILABLE FAULT CURRENT MARKINGS.
 - MUST COMPLY WITH FBC-E SECTION 405 MANDATORY LIGHTING
 CONTROLS A NOTE WILL SUFFICE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER