| Notes |
| Date |
Text |
| 2016-03-08 16:34:29 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1. KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO | | | THE BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL | | | FIRE ALARM CONDITION. | | | | | | NFPA 96 | | | | | | CHAPTER 10 FIRE-EXTINGUISHING EQUIPMENT | | | | | | 10.6 SYSTEM ANNUNCIATION. | | | | | | 10.6.1 UPON ACTIVATION OF AN AUTOMATIC | | | FIRE-EXTINGUISHING SYSTEM, AN AUDIBLE ALARM OR VISUAL | | | INDICATOR SHALL BE PROVIDED TO SHOW THAT THE SYSTEM HAS | | | ACTIVATED. | | | | | | 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING | | | THE OCCUPANCY WHERE THE EXTINGUISHING SYSTEM IS | | | LOCATED, THE ACTIVATION OF THE AUTOMATIC | | | FIRE-EXTINGUISHING SYSTEM SHALL ACTIVATE THE FIRE ALARM | | | SIGNALING SYSTEM. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|