| 2016-03-24 13:44:32 | BUILDING PLAN REVIEW |
| | W.P.B. REVISION: 16030229 |
| | W. P. B. PERMIT: 15070534 |
| | ADD: 4117 BROADWAY |
| | CONT: DREAMWORKS CONST. & REMOD. |
| | TEL: (813)249-5541 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W |
| | * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. MARCH 24/ 2016 |
| | ACTION: DENIED. |
| | |
| | NOTE THIS WAS A PROVISO UNDER THE PRIME PERMIT |
| | 15070534. THE COVERSHEET LIST VARIOUS PRODUCT |
| | APPROVALS. PLEASE SUBMIT THE ACTUAL PRODUCT APPROVALS |
| | FOR REVIEW FOR CODE COMPLIANCE. NO PRODUCTS SUBMITTED |
| | ON THE 2ND REVIEW CYCLE. |
| | BUILT UP ROOFING GAF FL # 477-R07 |
| | UNDERLAYMENT GAF FL # 10626-R12 |
| | FASTENERS OMG FL # 699-R07 |
| | INSULATION GAF FL # 16311-R4 |
| | |
| | 1) THE SUBMITTED PRODUCT APPROVAL IS A DIFFERENT |
| | APPROVAL FROM THE PRODUCT APPROVALS LISTED UNDER THE |
| | PRIME PERMIT. THE CONTRACTOR HAS HAD THE ENGINEER OF |
| | RECORD APPLY THEIR SHOP DRAWING STAMP OF APPROVAL BUT |
| | WITHIN THE DOCUMENT THERE ARE MANY SUB-SYSTEMS FOR |
| | INSULATED WOOD DECKS AS WELL AS NON-INSULATED WOOD |
| | DECKS WITH VARYING PRESSURES. NO SUB-SYSTEM HAS BEEN |
| | IDENTIFIED. PLEASE IDENTIFY WHICH SUB-SYSTEM IS TO BE |
| | APPLIED, THEN CIRCLE THE C EXPOSURE, ENCLOSED |
| | STRUCTURE, 15 FEET MEAN ROOF HEIGHT AND THE 170 MPH |
| | COLUMN. |
| | THIS WILL GIVE YOU THE REQUIRED FASTENING PATTERN FOR |
| | ROOF ZONES 2 & 3. |
| | |
| | 2) WE HAVE TALKED ON THE TELEPHONE ABOUT THIS JOB. |
| | FOLLOW THE INSTRUCTIONS THE INSPECTOR HAS GIVEN YOU, ON |
| | THE PERMIT CARD. |
| | 2A) PROVIDE INPROGRESS PICTURES OR AN ENGINEER'S |
| | INSPECTION REPORT. INPROGRESS INSPECTION MISSED. |
| | |
| | 2B) PROVIDE APPROVED PRODUCT APPROVALS. |
| | |
| | 3) THEN RECALL IN THE FINAL ROOFING INSPECTION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |