| Date |
Text |
| 2016-03-16 14:57:36 | 1) SHT. A-2 - TOILET ROOM CALCULATIONS - THE TABLE |
| | REFERENCED IS INCORRECT. THERE IS NO TABLE 400.1 IN THE |
| | 2014 FLORIDA PLUMBING CODE. THE CORRECT TABLE IS 403.1. |
| | PLEASE CORRECT. |
| | 2) CLEARLY SHOW THE LOCATION OF THE REQUIRED SERVICE |
| | SINKS FOR THE INSTITUTIONAL AND ASSEMBLY OCCUPANCIES AS |
| | REQUIRED BY 2014 FPC TABLE 403.1. |
| | 3) A MINIMUM OF ONE NEW WASHER AND ONE NEW DRYER IN THE |
| | EXISTING LAUNDRY AREA SHALL COMPLY WITH THE 2014 FBC |
| | ACCESS. SEC.611.1 - 611.4. |
| | 4) SHT. A-11, DETAIL #2 - SHOW THE REQUIRED 30 INCH |
| | WIDE MINIMUM BY 60 INCH LONG MINIMUM CLEAR FLOOR SPACE |
| | ADJACENT TO THE OPEN FACE OF THE ACCESSIBLE SHOWER. |
| | 5) GRAB BARS IN THE ACCESSIBLE ROLL-IN SHOWER WITH THE |
| | SEAT SHALL BE LOCATE DIN ACCORDANCE WITH THE 2014 FAC |
| | SEC.608.3.2. |
| | 6) THE CONTROLS IN THE ACCESSIBLE ROLL-IN SHOWER WITH |
| | THE SEAT SHALL COMPLY WITH THE FAC SEC.608.5.2. |
| | 7) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN ACCORDANCE |
| | WITH THE FAC SEC.608.6. |
| | 8) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH |
| | THE FAC SEC. 610.3, 610.3.1. |
| | 9) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER FAC SEC.609.4. |
| | 10) SHT. A-12 - DETAIL #1 - SHOW THE INSIDE CLEAR |
| | DIMENSIONS (L X W) OF THE ACCESSIBLE TOILET ROOM.THE |
| | MINIMUM WIDTH SHALL BE 85 INCHES. 2014 FAC SEC. 604.3, |
| | 606. |
| | 11) SHT.A-13 - DETAIL #5 - THE THRESHOLD AT THE |
| | ACCESSIBLE SHOWER SHALL BE A 1/2 INCH MAXIMUM PER 2014 |
| | FAC SEC.608.7. |
| | 12) SHT. P1.1 - THE PRINTING ON THE PLAN FOR THE WATER |
| | AND SANITARY SIZES & NOTES IS SO SMALL IT IS ILLEGIBLE. |
| | SUBMIT A CLEAR AND LEGIBLE PLAN. FBC 107.2.1. |
| | 13) SHT.P2.1 - DETAIL #10 SHOWS WATER HEATERS BUT IT IS |
| | LABELED AS "BACKFLOW PREVENTER ASSEMBLY."PLEASE |
| | CORRECT. |
| | 14) SHT. P2.1 - THE WATER HEATERS ARE SHOWN AS GAS. |
| | SUBMIT A COMPLETE GAS DRAWING COMPLYING WITH THE |
| | FOLLOWING ITEMS: |
| | |
| | 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| | G2413. |
| | |
| | 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER (IF |
| | APPLICABLE) OF THE CORRUGATED STAINLESS STEEL TUBING |
| | FOR EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | 3.) TYPE OF GAS (LP OR NATURAL). |
| | |
| | 4.) BTU LOAD OF EACH APPLIANCE / EQUIPMENT AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2014 |
| | FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413. |
| | |
| | 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN |
| | THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| | |
| | 6.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G |
| | 2407. |
| | |
| | 7.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| | SEC. G2413.2. . |
| | |
| | 8.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| | SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426. |
| | |
| | 9.) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. |
| | |
| | 10.) CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK ( DOT OR ASME ), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 11.) CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS |
| | ABOVE GROUND OR BELOW GROUND, AND SHOW THE METHOD OF |
| | REQUIRED PROTECTION FOR THE LP TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK IS BELOW GROUND IT SHALL BE |
| | ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, |
| | THE TANK SHALL BE SECURELY ANCHORED TO WITHSTAND 170 |
| | MPH ULT WIND LOAD PER THE FLORIDA BUILDING CODE. |
| | |
| | 15) THE BACKFLOW PREVENTION DEVICE SHALL BE LEAD FREE |
| | AND BE LISTED ON THE UNIVERSITY OF SOUTHERN |
| | CALIFORNIA"S (USC) LIST OF APPROVED DEVICES. |
| | 16) A SEPARATE PERMIT IS REQUIRED FOR THE NEW BACKFLOW |
| | PREVENTION DEVICE.A SEPARATE PERMIT APPLICATION SHALL |
| | BE SUBMITTED WITH TWO COPIES OF THE SPECIFICATIONS FOR |
| | THE DEVICE. |
| | 17) A CLEANOUT IS REQUIRED IN EACH WASTE OR SOIL STACK |
| | ( EXCEPT THE LAVATORY STACKS ) PER FPC SEC. 708.3.4. |
| | 18) SHT. P3.1 - THE WATER CLOSETS IN THE MEN'S BATH #4 |
| | & #5 ARE NOT VENTED. AS DRAWN, THEY ARE BEING WET |
| | VENTED AND CREATING A CODE VIOLATION OF SEC. 912.1 OF |
| | THE FPC FOR THE NUMBER AND TYPE OF FIXTURES ON THE WET |
| | VENT. INDIVIDUALLY VENTING THE TOILETS WILL SOLVE THIS |
| | PROBLEM. |
| | 19) SHT.P3.1 - BATH #3 - A VENT IS REQUIRED BETWEEN THE |
| | WATER CLOSET AND THE SHOWER. 2014 FPC SEC.901.2 & |
| | 901.2.1. |
| | 20) SHT. P3.1 - THE 3 INCH VENT IN RESTROOM #9 IS SHOWN |
| | AS A FLAT, DRY VENT AND IS NOT PERMITTED. THE VENT |
| | SHALL CONNECT TO A HORIZONTAL DRAIN ABOVE THE |
| | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FPC SEC.905.3. |
| | 21) SHT. P3.1 - SIZE ALL VENTS ON THE SANITARY RISER. |
| | 22) THE WASHING MACHINE SHALL BE INSTALLED ON A 3" |
| | STACK PER THE 2014 FPC SEC.406.2. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |