| 2016-03-14 08:43:12 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. ADD A NOTE TO INDICATE NEC 110.16 ARC-FLASH WARNING | | | LABELS REQUIRED. A NOTE WILL SUFFICE. | | | 2. ON SHEET E1.1 UPDATE ELECTRICAL NOTES TO INDICATE | | | NEC 2011 NOT 2005 CODE EDITION. | | | 3. PROVIDE A NOTE TO INDICATE SEPARATE PERMITS REQUIRED | | | FOR ANY LOW VOLTAGE SYSTEMS | | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|