| 2016-03-21 06:40:40 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030222 |
| | ADD: 5400 EAST AVENUE |
| | CONT: STUART & SHELBY DEVELOPMENT |
| | TEL: 561-637-7902 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 18/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A9 INDICATES THE WINDOW AND EXTERIOR DOOR |
| | POSITIVE & NEGATIVE PRESSURES. PLEASE PROVIDE WHERE THE |
| | WIND DESIGN CRITERIA CAN BE LOCATED IN THE PLANS. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. |
| | ASCE 7-10. |
| | |
| | 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2). |
| | |
| | 2) SHEET A7 SHOWS A WHITE BAHAMA STYLE SHUTTER, PLEASE |
| | PROVIDE IF THIS RIGID AWNING WILL STAY AS POSITIONED OR |
| | REPOSITIONED TO CLOSE AN OPENING WHEN THE BUILDING IS |
| | UNATTENDED OR ACT AS A STORM SHUTTER, THE DESIGN IN THE |
| | CLOSED POSITION SHALL ALSO COMPLY WITH CHAPTER 16 AND |
| | SHALL BE IMPACT RESISTANT IN ACCORDANCE WITH SECTION |
| | 1609.1.2 FBC-B. |
| | |
| | 3) SHEET A7 & 8 BOTH SHOW DETAILS OF CULTURED STONE |
| | VENEER 2008 MIST DRYSTACK LEDGESTONE OWENS CORNING. |
| | PLEASE SUBMIT THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. THE PLANS DO NOT INDICATE IF THE STONE IS |
| | ATTACHED OR ADHERED. PLEASE PROVIDE COMPLIANCE WITH ONE |
| | OF THESE CODE SECTIONS: |
| | 2014 FBC-B 1405.6. ANCHORED MASONRY VENEERS |
| | 1405.7 STONE VENEERS |
| | 1405.10 ADHERED MASONRY VENEERS |
| | 1405.10.2 EXTERIOR ADHERED MASONRY VENEERS/ PORCELAIN |
| | TILE. |
| | |
| | 4) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN AN AH |
| | FLOOD ZONE. FBC BUILDING 1612 AND CITY OF WPB CODE OF |
| | ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| | "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. PLEASE REVIEW CITY ORDINANCE FOR THE CITY |
| | REQUIREMENTS REQUIRE AN ADDITIONAL 6 INCHES OF |
| | ELEVATION. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (2) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 2ND FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31/2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 5) SHEET M1.1 SHOWS A NEW ROOF TOP RTU # 9 PLEASE |
| | PROVIDE ENGINEERING FOR THE FRAMING AROUND THE NEW ROOF |
| | TOP HOLE FOR THIS UNIT. ALSO PROVIDE THE MANUFACTURERS |
| | INSTALLATION INSTRUCTIONS, IF A PRODUCT APPROVAL PLEASE |
| | PROVIDE AS WELL AS THE TIE DOWN OF THE RTU TO THE CURB. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31(D) ROOFING PRODUCTS AND ASSEMBLIES/ CURBS/ ROOF TOP |
| | FANS |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF DECK AS WELL AS FROM |
| | THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014 |
| | FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 6) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 7) IF ZONING REQUIRES A MECHANICAL EQUIPMENT SCREEN FOR |
| | THE NEW ROOF TOP EQUIPMENT THEN SHOW COMPLIANCE WITH: |
| | FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS. |
| | MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF |
| | THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN |
| | ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER |
| | THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS |
| | SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| | FIRE-RESISTANCE RATING REQUIREMENTS. |
| | |
| | SHEET A4 SHOWS NEW TRAY SLIDES BY OTHERS, PLEASE SHOW |
| | COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE: |
| | |
| | 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE |
| | 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |