2016-03-03 17:56:50REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014) , NEC 2011
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND LISTING
 INFORMATION FOR THE ELECTRICAL POOL HEATER. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF LOAD CALCULATIONS TO SHOW THAT
 THE EXISTING ELECTRICAL SERVICE IS ADEQUATE FOR THE
 POOL PUMP AND HEATER LOADS. THE NAME AND LICENSE NUMBER
 OF THE PERSON PERFORMING THE CALCULATIONS ARE REQUIRED
 ON THE CALCULATIONS. FBC 107.2.1
  