| Plan Review Notes For Permit 16030122 |
| Permit Number |
16030122 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-17 15:51:29 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030122 | | | 3/17/16 | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL | | | EXISTS, PLEASE COMPLY. | | | NEW AHRI CERTIFICATES HAVE BEEN SUBMITTED FOR AC | | | SYSTEMS THAT DON'T MATCH THE SYSTEMS SHOWN ON THE | | | PLANS. PLEASE REVISE THE AC SCHEDULES ON THE PLANS TO | | | MATCH THE CERTIFICATES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|