| Plan Review Notes For Permit 16030122 |
| Permit Number |
16030122 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-07 08:52:59 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030122 | | | 3/7/16 | | | | | | 1) NEW AHRI CERTIFICATES HAVE BEEN SUBMITTED FOR AC | | | SYSTEMS THAT DON'T MATCH THE SYSTEMS SHOWN ON THE | | | PLANS. PLEASE REVISE THE PLANS. | | | 2) CHANGE THE 12X6 SW DIFFUSER IN THE KITCHEN TO 14X6. | | | 3) SUBMIT A SUB-PERMIT APPLICATION FROM A LICENSED AC | | | CONTRACTOR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|