Plan Review Notes
Plan Review Notes For Permit 16030080
Permit Number 16030080
Review Stop G
Sequence Number 2
Notes
Date Text
2016-05-09 11:07:391) THE SUBMITTED PLANS STILL INCLUDE COPIES OF GAS
 SIZING TABLES FOR SCH. 40 METALLIC PIPE AND ALSO FOR
 CSST. THERE IS NO METALLIC PIPE OR CSST SHOWN ON THE
 PLANS. SUBMIT TWO COPIES OF A COMPLETE GAS LAYOUT
 SHOWING THE TYPES OF PIPE BEING INSTALLED AND WHERE. IF
 THE CSST IS NOT BEING INSTALLED, REMOVE THE SIZING
 TABLE FROM THE PACKAGE. FBC 107.2.1.
 2) THE SUBMITTED PLANS HAVE SIZING TABLES FOR PE PIPE
 AND ALSO FOR PE TUBING. WHICH IS IT? SUBMIT COPIES OF
 THE CORRECT SIZING TABLES FOR THE CORRECT TYPE OF PIPE
 MATERIAL BEING INSTALLED.
 3) FOUR DIFFERENT GAS SIZING TABLES FOR PE PIPE HAVE
 BEEN SUBMITTED FOR REVIEW AND THEY ARE ALL FOR AN INLET
 PRESSURE OF LESS THAN 2 PSI BUT THE PLANS SHOW AN INLET
 PRESSURE OF 2 PSI. CLARIFY.
 4) SHOW THE TOTAL DEVELOPED LENGTH FROM EACH STEP DOWN
 REGULATOR TO THE APPLIANCE SERVED AND SHOW THE TYPE OF
 PIPE ON THE PLANS FROM THE STEP DOWN REGULATOR TO THE
 APPLIANCE. SUBMIT THE CORRECT SIZING TABLE FROM THE
 2014 FUEL GAS CODE. FBC 107.2.1.
 5) SOME OF THE SIZING TABLES SUBMITTED ARE STILL FROM
 AN OUTDATED EDITION OF THE FUEL GAS CODE.THE CODE IN
 EFFECT IS THE 2014 FLORIDA BUILDING CODE, FUEL GAS
 WHICH IS BASED ON THE 2012 ICC CODE, NOT THE
 2009.SUBMIT COPIES OF THE CORRECT SIZING TABLES FROM
 THE CODE THAT IS CURRENTLY IN EFFECT.
 6) REMOVE ALL DOCUMENTS THAT ARE NOT APPLICABLE TO THIS
 INSTALLATION. THIS SUBMITTAL IS TOO CONFUSING TO
 PERFORM A COMPREHENSIVE REVIEW.
 7) THE WORK ORDER/INVOICE SHOWS 63 FEET OF PE PIPE TO
 BE INSTALLED AND ALSO 50 FEET. WHICH IS IT? CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  