| Plan Review Notes For Permit 16030080 |
| Permit Number |
16030080 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-23 03:29:20 | 1) THE SUBMITTED PLANS INCLUDE COPIES OF GAS SIZING | | | TABLES FOR SCH. 40 METALLIC PIPE AND ALSO FOR CSST. | | | THERE IS NO METALLIC PIPE OR CSST SHOWN ON THE PLANS. | | | SUBMIT TWO COPIES OF A COMPLETE GAS LAYOUT SHOWING THE | | | TYPES OF PIPE BEING INSTALLED AND WHERE. IF THE CSST IS | | | NOT BEING INSTALLED, REMOVE THE SIZING TABLE FROM THE | | | PACKAGE. FBC 107.2.1. | | | 2) SHOW THE LOCATION OF THE STEP DOWN REGULATORS & SHUT | | | OFF VALVES ON THE RISER. FBC 107.2.1. | | | 3) SHOW THE TOTAL DEVELOPED LENGTH FROM THE STEP DOWN | | | REGULATORS TO THE APPLIANCE. | | | 4) THE SIZING TABLES SUBMITTED ARE FROM AN OUTDATED | | | EDITION OF THE FUEL GAS CODE.THE CODE IN EFFECT IS THE | | | 2014 FLORIDA BUILDING CODE, FUEL GAS WHICH IS BASED ON | | | THE 2012 ICC CODE, NOT THE 2009.SUBMIT 2 CCOPIES OF THE | | | SIZING TABLES FROM THE CODE THAT IS CURRENTLY IN | | | EFFECT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|