| 2016-12-16 18:25:35 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 5TH REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) AS WE DISCUSSED PREVIOUSLY, YOU HAVE INDICATED THAT |
| | YOU ARE NOT ABLE TO INSTALL THE REQUIRED R-30 CEILING |
| | INSULATION. THEREFORE, YOU CAN NOT USE THE PRESCRIPTIVE |
| | METHOD TO SHOW COMPLIANCE WITH THE FBC ENERGY |
| | CONSERVATION. YOU SUBMITTED MANUAL J CALCULATIONS WHICH |
| | ARE USED TO SIZE THE HEATING AND COOLING EQUIPMENT. YOU |
| | WERE REQUESTED TO SUBMIT TWO SETS OF ENERGY COMPLIANCE |
| | FORMS TO SHOW THAT THE BUILDING ENVELOPE MEETS THE FBC |
| | ENERGY CONSERVATION REQUIREMENTS. SUBMIT TWO SETS OF |
| | THE DOCUMENTS REQUIRED BY FBC ENERGY CONSERVATION |
| | SECTION R101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) |
| | DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR |
| | COMPLIANCE BY SECTION R405. |
| | |
| | 2) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN |
| | PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO. |
| | 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS |
| | 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY |
| | LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. THIS COMMENT |
| | HAS NOT BEEN ADDRESSED. ( IF YOU ELECT TO DO SO, THIS |
| | CAN BE SUBMITTED FOR REVIEW AT A LATER DATE. HOWEVER, |
| | IT WILL HAVE TO BE REVIEWED AND APPROVED BEFORE THE |
| | ROOFING IS INSTALLED. ) |
| | |
| | 3) THE PLANS WILL NEED TO BE REVIEWED BY PALM BEACH |
| | COUNTY TO DETERMINE IF ANY IMPACT FEES ARE DUE. |
| | |
| | |