| 2016-11-21 18:53:35 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT ENERGY COMPLIANCE FORMS TO SHOW THAT THE NEW |
| | ADDITION MEETS THE FBC ENERGY CONSERVATION |
| | REQUIREMENTS. FBC ENERGY CONSERVATION R402.1 THE ENERGY |
| | FORM R402-2014 THAT WAS SUBMITTED CONTAINS NUMEROUS |
| | ERRORS AND OMISSIONS. THE OWNER'S NAME, BUILDER AND |
| | PERMITTING OFFICE (WEST PALM BEACH) ARE NOT LISTED AT |
| | THE TOP OF THE FORM. THE OWNER/AGENT SIGNATURE AND DATE |
| | IS MISSING. ON PAGE TWO FOR THE FLOORS THE R-VALUE IS |
| | SPECIFIED AS R-13. ON PAGE 1 FOR SLAB ON GRADE THE |
| | R-VALUE SHOULD BE NR RATHER THAN NA. THE DUCTWORK IS |
| | SPECIFIED AS R-16 ON PAGE 2 AND R-10 ON PAGE 1. THE |
| | CEILING INSULATION IS SPECIFIED AS R-30, WHICH REQUIRES |
| | MORE SPACE THAN THE 7-1/4 INCHES THAT THE 2 X 8 ROOF |
| | JOISTS PROVIDE. SOME OF THE INSULATION R-VALUES |
| | SPECIFIED ON THE PLANS DO NOT MATCH WHAT IS LISTED ON |
| | THE FORM. |
| | |
| | 2) THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON |
| | SHEET S-2 ARE INCORRECT. THIS STRUCTURE HAS A FLAT ROOF |
| | AND A 14' ROOF HEIGHT PER THE PLANS. THE WIND SPEED IS |
| | 170MPH VULT, 132MPH VASD. THE EXPOSURE CATEGORY IS C. |
| | FBC-R301.2.1 FOR EXAMPLE: THE WORST CASE FOR A 10SQFT |
| | AREA IN WALL ZONE 5 IS +37.9, -50.7 PSF IN EXPOSURE C, |
| | 132MPH VASD WITH A 15' MEAN ROOF HEIGHT. (PREVIOUS |
| | COMMENT) PLEASE HAVE A FLORIDA LICENSED ENGINEER REVIEW |
| | THE COMPONENT AND CLADDING PRESSURES AND MAKE |
| | CORRECTIONS TO THE PLANS. |
| | |
| | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. (PREVIOUS COMMENT) THE PRODUCT |
| | APPROVALS ARE REQUIRED TO BE APPROVED IN WRITING BY THE |
| | ARCHITECT. |
| | |
| | 4) SPECIFY THE SYSTEM TYPE, FASTENING OPTION AND DESIGN |
| | PRESSURE FOR THE GAF BUR ROOFING ASSEMBLY (NOA NO. |
| | 13-1022.15). SUBMIT TWO SETS OF SIGNED AND SEALED RAS |
| | 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY |
| | LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA. |
| | |
| | 5) THE MASTER BEDROOM IS MISLABELED AS THE MASTER |
| | BATHROOM ON A-1. FBC 107.2.1 |
| | |
| | 6) PROVIDE THE FLORIDA PRODUCT APPROVAL FL NUMBER FOR |
| | THE EXTERIOR DOOR THAT WILL BE USED. FBC 107.3.4 |
| | (PREVIOUS COMMENT) THERE IS NO FL NUMBER ON THE DOOR |
| | PRODUCT APPROVALS. |
| | |
| | 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |