| 2016-09-13 11:37:37 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 5TH REVIEW |
| | DATE: TUES. SEPT. 09/13/2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | 6 UNIT/ R2 / APARTMENT BUILDING |
| | |
| | 1) SHEET A3.1 & A3.2 SHOWS A WINDOW SCHEDULE, IN EACH |
| | BEDROOM THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE |
| | EGRESS REQUIREMENTS, SEE THE MIDDLE APARTMENTS 2 & 5 |
| | BEDROOM # 2 IN EACH. THE WINDOW SCHEDULE SHOWS WINDOW |
| | STYLE (H) SINGLE HUNG WINDOW. THE OPENING SIZE IS 6-0X |
| | 4-2 IN THE ELEVATIONS THE 6 FOOT DIMENSION IS A |
| | HORIZONTAL MEASUREMENT AND MULLION BETWEEN THE 2 |
| | WINDOWS. WINDOWS MUST MEET THE REQUIREMENTS OF THE 2014 |
| | FBC-B 1029 EMERGENCY ESCAPE & RESCUE. |
| | |
| | 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING |
| | OF 5.7 SQUARE FEET (0.53 M2). |
| | EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE |
| | FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 |
| | SQUARE FEET (0.46 M2). |
| | |
| | FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET |
| | CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 |
| | MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION |
| | SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING |
| | DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF |
| | THE OPENING. |
| | |
| | FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE |
| | CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM) |
| | MEASURED FROM THE FLOOR. |
| | |
| | 2) BUILDING PROVISO: DEFERRED SUBMITTAL. 107.3.4.2. |
| | CONTRACTOR TO SUBMIT TESTING REPORTS TO THE DESIGNER OF |
| | RECORD FOR REVIEW BEFORE SUBMITTING TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | PROVIDE FLOOR ASSEMBLY TYPE WITH FLOOR INSULATION WHERE |
| | EITHER, TILE, VINYL TILE OR LAMINATED WOODS OCCUR ON |
| | THE 2ND FLOOR. |
| | (FBC-B 2014) FOR TILE, STONE, MARBLE AND WOOD FLOORING |
| | ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED TO |
| | THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 |
| | 720.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | 3) BUILDING PROVISO: DEFERRED SUBMITTALS: 2014 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |