Plan Review Notes
Plan Review Notes For Permit 16030064
Permit Number 16030064
Review Stop B
Sequence Number 5
Notes
Date Text
2016-09-13 11:37:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: TUES. SEPT. 09/13/2016
 ACTION: BUILDING PROVISO
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 1) SHEET A3.1 & A3.2 SHOWS A WINDOW SCHEDULE, IN EACH
 BEDROOM THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE
 EGRESS REQUIREMENTS, SEE THE MIDDLE APARTMENTS 2 & 5
 BEDROOM # 2 IN EACH. THE WINDOW SCHEDULE SHOWS WINDOW
 STYLE (H) SINGLE HUNG WINDOW. THE OPENING SIZE IS 6-0X
 4-2 IN THE ELEVATIONS THE 6 FOOT DIMENSION IS A
 HORIZONTAL MEASUREMENT AND MULLION BETWEEN THE 2
 WINDOWS. WINDOWS MUST MEET THE REQUIREMENTS OF THE 2014
 FBC-B 1029 EMERGENCY ESCAPE & RESCUE.
  
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADE
 FLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5
 SQUARE FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL. 107.3.4.2.
 CONTRACTOR TO SUBMIT TESTING REPORTS TO THE DESIGNER OF
 RECORD FOR REVIEW BEFORE SUBMITTING TO THE BUILDING
 DEPARTMENT.
  
 PROVIDE FLOOR ASSEMBLY TYPE WITH FLOOR INSULATION WHERE
 EITHER, TILE, VINYL TILE OR LAMINATED WOODS OCCUR ON
 THE 2ND FLOOR.
 (FBC-B 2014) FOR TILE, STONE, MARBLE AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 3) BUILDING PROVISO: DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  