2016-05-23 15:01:30REVIEW: FBC 2014
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENT:
  
  
  
 1) HAS NOT COMPLIED : THE CONTRACTOR NEEDS TO SPLIT
 THIS PERMIT PACKAGE INTO (2) SEPARATE PERMITS AND PLANS
 SINCE THERE ARE (2) TYPES OF BUILDINGS BEING RENOVATED.
 A COMMERCIAL APARTMENT BUILDING ( COMMERCIAL REMODEL)
 AND A SINGLE FAMILY DWELLING( RESIDENTIAL REMODEL)
 UNLESS THERE IS A USE THAT HAS NOT BEEN DECLARED SUCH
 AS A SOBER HOME, HALF-WAY HOUSE, ETC... NOTE THERE ARE
 (2) DIFFERENT OCCUPANCY TYPE R2 & R3 AND NEED TO BE
 REVIEWED UNDER THEIR APPROPRIATE CODES (FBC-BUILDING &
 FBC-RESIDENTIAL) AS WELL AS FOR INSPECTION PURPOSE AND
 FOR RECORD KEEPING .
  
 2. THE DEMO PLAN FOR SINGLE FAMILY HOME SHOWS DEMO WORK
 BUT THERE'S NO INDICATION OF WHAT PLUMBING WORK IS
 BEING DONE PLEASE CLARIFY. PER. WPB AMEND TO FBC
 107.2.1
  
 3. IN BOTH SETS OF PLANS THERE ARE DUPLICATE PAGES IN
 PLUMBING PLEASE REMOVE ALSO MARK AS VOID OR REMOVE
 PREVIOUSLY STAMPED PAGE. . PER. WPB AMEND TO FBC
 107.2.1
  
 4. THE BACK FLOW SUBMITTED FOR THE FIRE SPRINKLER DOES
 NOT MEET LEAD FREE REQUIREMENTS ALL BACK FLOWS SHALL
 MEET THESE REQUIREMENTS
 A) TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE
 DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 B) ALL BACKFLOW DEVICES MUST BE LEAD FREE.
  
 C) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 D) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 E) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR
 QUESTIONS REGARDING PERMITTING REQUIREMENTS MAY BE
 DIRECTED TO:
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  