| 2016-06-02 14:18:49 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: 06/02/2016/ 07/12/2016 (OLD VOIDED SHEETS |
| | REMOVED) |
| | ACTION: DENIED |
| | |
| | |
| | 6 UNIT/ R2 / APARTMENT BUILDING |
| | |
| | 1-2) CORRECTED. |
| | |
| | 3A-B) COMPLIED. |
| | |
| | 3C) 2014 FBC-B SECTIONS 420.2 & 708.4 FOR |
| | TENANTSEPERATION WALL REQUIREMENTS. NOTE THE PLAN SHOWS |
| | THE WALL FIRE RATING STOPPING AT THE CEILING LINE, NOT |
| | CONTINIOUS IN THE FLOOR JOIST. THE PLANS ARE SILENT |
| | ABOUT THE 2ND FLOOR ABOVE THE CEILING LINE. |
| | |
| | FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING |
| | UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING |
| | UNITS IN THE SAME BUILDING AND WALLS SEPARATING |
| | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| | CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 708. |
| | |
| | 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| | TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| | TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| | OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. IN COMBUSTIBLE |
| | CONSTRUCTION WHERE THE FIRE PARTITIONS ARE NOT REQUIRED |
| | TO BE CONTINUOUS TO THE SHEATHING, DECK OR SLAB, THE |
| | SPACE BETWEEN THE CEILING AND THE SHEATHING, DECK OR |
| | SLAB ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN |
| | ACCORDANCE WITH SECTIONS 718.2 AND 718.3 AT THE |
| | PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE |
| | PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING |
| | OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING |
| | TENANT SPACES IN COVERED AND OPEN MALL BUILDINGS, WALLS |
| | SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING |
| | UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB, |
| | IIIB AND VB CONSTRUCTION. |
| | |
| | 3D) SHEET A3.1 SHOWS A WINDOW SCHEDULE, IN EACH BEDROOM |
| | THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE EGRESS |
| | REQUIREMENTS OF: |
| | 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING |
| | OF 5.7 SQUARE FEET (0.53 M2). |
| | EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR |
| | EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE |
| | FEET (0.46 M2). |
| | |
| | FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET |
| | CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 |
| | MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION |
| | SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING |
| | DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF |
| | THE OPENING. |
| | |
| | FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE |
| | CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM) |
| | MEASURED FROM THE FLOOR. |
| | |
| | 3E) COMPLIED. |
| | |
| | 3F) . THE PLANS DO NOT INDICATE A CUT SECTION THROUGH |
| | THE FLOOR/ CEILING ASSEMBLY OF THE 1ST FLOOR CEILING. |
| | THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2 |
| | HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS |
| | SHOWING THE ASSEMBLY. |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS |
| | (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | & CEILINGS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES |
| | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. |
| | |
| | 3G-K) COMPLIED. |
| | |
| | 4A) COMPLIED. |
| | |
| | 4B) SHEET A3.2 THE 2ND FLOOR PORCH THE WINDOWS IN UNIT |
| | # 5 BEDROOM # 5 & THE LIVING ROOM ARE NOT IDENTIFIED. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NOTE |
| | THESE WINDOWS WILL HAVE TO BE SAFETY WINDOWS AS WELL |
| | LOCATED IN A HAZARDOUS LOCATION. NOTE THIS SAME |
| | SITUATION OCCURS ON THE 1ST FLOOR. HAZARDOUS LOCATION A |
| | WALKABLE PATH ADJACENT TO THE EXTERIOR OF THE WINDOW. |
| | 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS. |
| | THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH |
| | 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS |
| | LOCATIONS REQUIRING SAFETY GLAZING MATERIALS. |
| | |
| | 5) BUILDING PROVISO: PROVIDE FLOOR ASSEMBLY TYPE WITH |
| | FLOOR INSULATION WHERE EITHER, TILE, VYNAL TILE OR |
| | LAMINATED WOODS OCCUR ON THE 2ND FLOOR. |
| | (FBC-B 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 5B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 |
| | 720.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | 6) DEFERRED SUBMITTALS: 2014 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. JUNE 02/ 2016 |
| | ACTION: |
| | |
| | HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE |
| | |
| | 1) AT LEAST ONE WINDOW IN EACH BEDROOM SHALL COMPLY |
| | WITH: |
| | 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING |
| | OF 5.7 SQUARE FEET (0.53 M2). |
| | EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR |
| | EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE |
| | FEET (0.46 M2). |
| | |
| | FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET |
| | CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 |
| | MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION |
| | SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING |
| | DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF |
| | THE OPENING. |
| | |
| | FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE |
| | CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM) |
| | MEASURED FROM THE FLOOR. |
| | |
| | |
| | 2) DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | DEFERRED SUBMITTAL 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | |