2016-06-02 14:18:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: 06/02/2016/ 07/12/2016 (OLD VOIDED SHEETS
 REMOVED)
 ACTION: DENIED
  
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 1-2) CORRECTED.
  
 3A-B) COMPLIED.
  
 3C) 2014 FBC-B SECTIONS 420.2 & 708.4 FOR
 TENANTSEPERATION WALL REQUIREMENTS. NOTE THE PLAN SHOWS
 THE WALL FIRE RATING STOPPING AT THE CEILING LINE, NOT
 CONTINIOUS IN THE FLOOR JOIST. THE PLANS ARE SILENT
 ABOUT THE 2ND FLOOR ABOVE THE CEILING LINE.
  
 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO. IN COMBUSTIBLE
 CONSTRUCTION WHERE THE FIRE PARTITIONS ARE NOT REQUIRED
 TO BE CONTINUOUS TO THE SHEATHING, DECK OR SLAB, THE
 SPACE BETWEEN THE CEILING AND THE SHEATHING, DECK OR
 SLAB ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN
 ACCORDANCE WITH SECTIONS 718.2 AND 718.3 AT THE
 PARTITION LINE. THE SUPPORTING CONSTRUCTION SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE WALL SUPPORTED, EXCEPT FOR WALLS SEPARATING
 TENANT SPACES IN COVERED AND OPEN MALL BUILDINGS, WALLS
 SEPARATING DWELLING UNITS, WALLS SEPARATING SLEEPING
 UNITS AND CORRIDOR WALLS, IN BUILDINGS OF TYPE IIB,
 IIIB AND VB CONSTRUCTION.
  
 3D) SHEET A3.1 SHOWS A WINDOW SCHEDULE, IN EACH BEDROOM
 THERE HAS TO BE AT LEAST ONE WINDOW MEETING THE EGRESS
 REQUIREMENTS OF:
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE
 FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 3E) COMPLIED.
  
 3F) . THE PLANS DO NOT INDICATE A CUT SECTION THROUGH
 THE FLOOR/ CEILING ASSEMBLY OF THE 1ST FLOOR CEILING.
 THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2
 HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS
 SHOWING THE ASSEMBLY.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 & CEILINGS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3G-K) COMPLIED.
  
 4A) COMPLIED.
  
 4B) SHEET A3.2 THE 2ND FLOOR PORCH THE WINDOWS IN UNIT
 # 5 BEDROOM # 5 & THE LIVING ROOM ARE NOT IDENTIFIED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NOTE
 THESE WINDOWS WILL HAVE TO BE SAFETY WINDOWS AS WELL
 LOCATED IN A HAZARDOUS LOCATION. NOTE THIS SAME
 SITUATION OCCURS ON THE 1ST FLOOR. HAZARDOUS LOCATION A
 WALKABLE PATH ADJACENT TO THE EXTERIOR OF THE WINDOW.
 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS.
 THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH
 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS.
  
 5) BUILDING PROVISO: PROVIDE FLOOR ASSEMBLY TYPE WITH
 FLOOR INSULATION WHERE EITHER, TILE, VYNAL TILE OR
 LAMINATED WOODS OCCUR ON THE 2ND FLOOR.
 (FBC-B 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5C) NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 6) DEFERRED SUBMITTALS: 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JUNE 02/ 2016
 ACTION:
  
 HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE
  
 1) AT LEAST ONE WINDOW IN EACH BEDROOM SHALL COMPLY
 WITH:
 2014 FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET (0.53 M2).
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE
 FEET (0.46 M2).
  
 FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
  
 2) DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 DEFERRED SUBMITTAL 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  