| 2016-04-22 15:15:19 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030064 | | | 4/22/16 | | | | | | 1) SHEETS M-1.1 & M-1.3 APARTMENT BUILDING: THE 1.5 TON | | | AC SYSTEM SPECIFIED FOR UNIT #2 WILL ONLY PRODUCE 600 | | | CFM'S OF SUPPLY AIR HOWEVER THE PLAN INDICATES A TOTAL | | | SUPPLY OF 665 CFM'S | | | 2) M-1.1 & M-1.2: THE PLANS DO NOT INDICATE HOW MINIMUM | | | O/A FOR LIVING AREAS AND MINIMUM KITCHEN EXHAUST WILL | | | BE PROVIDED- SEE TABLE 403.3 AND SHOW COMPLIANCE. | | | 3) M-1.1 & M-1.2: IF REVISING THE AC FLOOR PLANS PLEASE | | | PRINT THE DIMENSIONS OF ALL MAIN TRUNK DUCTS. | | | 4) M-1.1: PROVIDE WIND LOAD ENGINEERING FOR | | | INSTALLATION OF THE CONDENSER PADS AND TIE DOWN OF THE | | | NEW CONDENSERS- SECTION 301.15 | | | 4) M1.3, SINGLE FAMILY: SHOW THE LOCATIONS OF THE | | | CONDENSERS AND PROVIDE WINDLOAD ENGINEERING FOR TIE | | | DOWN OF THE NEW CONDENSERS PER SECTION M1301.1 FBC-14 | | | RESIDENTIAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|