Plan Review Notes
Plan Review Notes For Permit 16030064
Permit Number 16030064
Review Stop B
Sequence Number 2
Notes
Date Text
2016-04-21 07:54:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. APRIL 21/ 2016
 ACTION: DENIED
  
 NOTICE!!!!!!! !!!!!!!!!!!!! CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
 PLEASE READ!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY OLD AND OR VOIDED
 SHEETS & REPLACE ANY PAGES AS NECESSARY. OLD SHEETS
 LEFT IN PLANS. REVIEW FAILS.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 6 UNIT/ R2 / APARTMENT BUILDING
  
 1) CORRECTED. 2ND REQUEST.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. .
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 2) 2ND REQUEST. THE COVER-SHEET A-0.0 UNDER THE HEADING
 PROJECT DATA;
  
 2A) 2ND REQUEST. UNDER THE WIND DESIGN THE PLANS ONLY
 LIST THE R2 OCCUPANCY NOT THE R3 SINGLE FAMILY UNIT.
 PLANS AND DESIGN CRITERIA NEED TO BE SPLIT INTO 2
 PERMITS AND PACKAGES SO EACH BUILDING AND ASSOCIATED
 OCCUPANCY CAN BE REVIEWED UNDER THE APPROPRIATE CODE.
 107,2,1,4,
  
 2B) ) 2ND REQUEST. THE PROJECT DATA SHEET INDICATES
 THIS IS A LEVEL II ALTERATION. IT APPEARS MORE LIKE A
 LEVEL II LIMITED ALTERATION.2014 FBC-EXIST. BLDG. CODE
 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY WHERE THE WORK
 AREA EXCEEDS 50 PERCENT OF THE AGGREGATE AREA OF THE
 BUILDING. THIS REVIEW WILL BE TREATED AS SUCH, PLEASE
 UPDATE PLANS.
  
 2C) 2ND REQUEST. UNDER THE HEADING PROJECT DATA THERE
 ARE (2) CODES THAT ARE MISSING IN THE DESIGN CRITERIA,
 FOR THE COMMERCIAL 6 UNIT APARTMENT BUILDING THE 2014
 FBC-BUILDING, AND FOR THE SINGLE FAMILY DWELLING UNIT
 THE 2014 FBC-RESIDENTIAL CODE, 2 SEPARATE AND DISTINCT
 CODES. THE RESIDENTIAL CODE DEALS STRICTLY WITH 1-2
 FAMILY DWELLING UNITS!!!!!!!!!! SEE SCOPING AND TITLE
 REQUIREMENTS IN EACH CODE. 101.1 TITLE/ SCOPE 101.2..
  
 2D) COMPLIED. UNDER THE HEADING APARTMENT BUILDING
 SCOPE OF WORK THE PLANS INDICATE THIS IS A 6 STORY
 BUILDING. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2E)2ND REQUEST. THE PLANS DO NOT DECLARE IF THIS
 BUILDING IS FIRE SPRINKLERED OR NOT. IF FIRE
 SPRINKLERED WHAT TYPE OF FIRE SPRINKLER IS DESIGN?
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS.
  
 2F) COMPLIED
  
 2G) COMPLIED..
  
 3) 2ND REQUEST. CODE SUMMARY. SHEET A-3.3 ALL INDICATE
 THE PLANS WERE DESIGNED TO THE 2014 FLORIDA BUILDING
 CODE. PLEASE NOTE THE 2014 FLORIDA BUILDING CODE IS FOR
 COMMERCIAL BUILDINGS (APARTMENT BUILDINGS / R2). THIS
 SHEET IS THE FLOOR PLAN FOR THE SINGLE FAMILY HOUSE
 (R3). THE CODE FOR THE SINGLE FAMILY HOUSE IS THE 2014
 FBC-RESIDENTIAL CODE.
  
  
 SHEET A-3.1 / 1ST FLOOR PLAN OF THE 2 STORY R2
 APARTMENT BUILDING. TITLE BLOCK INDICATES 1ST FLOOR
 ELECTRIC PLAN?????? THIS PLAN APPEARS TO BE THE
 ARCHITECTURAL PLAN.
  
  
 3A) 2ND REQUEST. THE DESIGNER OF RECORD HAS DECLARED
 THIS BUILDING TYPE AS A I-B BUILDING TYPE OF
 CONSTRUCTION, SEE CODE SUMMARY TABLE 503 HEADING.
 PLEASE NOTE ALL TRUSSES AND ROOF SHEATHING HAD TO BE
 INSTALLED WITH FIRE RETARDANT TREATED PLYWOOD. ALL NEW
 FRAMING MEMBERS AND ROOF SHEATHING WILL NEED TO COMPLY
 WITH FBC-B 603.1.1.3. 1. FIRE-RETARDANT-TREATED WOOD
 SHALL BE PERMITTED IN: 1.3. ROOF CONSTRUCTION,
 INCLUDING GIRDERS, TRUSSES, FRAMING AND DECKING.
  
 3B) 2ND REQUEST. CODE SUMMARY ON THIS SHEET LIST A LOT
 OF CODE SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT
 CODE THESE SECTIONS WERE TAKEN FROM, NOT FOUND IN THE
 2014 FBC-EXISTING BUILDING CODE NOR THE 2014
 FBC-BUILDING CODE.
  
 3C) 2ND REQUEST. DETAIL 1/ A-4 OF SHEET A-3.1
 REFERENCES THE SFBC ITEM # 79 SECT. 37B. PLEASE UPDATE
 PLANS TO THE CURRENT 2014 FBC-B AND CURRENT CODE
 SECTIONS FOR TENANT SEPARATION REQUIREMENTS FOR TENANT
 SEPARATION WALLS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING
 UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING
 UNITS IN THE SAME BUILDING AND WALLS SEPARATING
 DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES
 CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE
 CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH
 SECTION 708.
  
  
 3D) 2ND REQUEST. IN UNIT # 2 THE WINDOWS IN THE BEDROOM
 #1, BATHROOM & KITCHEN ARE NOT IDENTIFIED. NOR ARE THE
 WINDOWS IN THE WINDOW SCHEDULE D-G NOT IDENTIFIED AS TO
 SIZE AND TYPE OF WINDOW. THE WINDOW SCHEDULE DOES NOT
 EVEN IDENTIFY THERE IS A WINDOW TYPE H LOCATED ON THE
 PLANS.
  
 3E) 2ND REQUEST. PLEASE PROVIDE WHAT THE SILL HEIGHT OF
 THE WINDOW IS LOCATED IN THE BATHROOMS, PLEASE SHOW
 COMPLIANCE WITH FBC-B 2406.4.5.
  
 3F) 2ND REQUEST. THE PLANS DO NOT INDICATE A CUT
 SECTION THROUGH THE FLOOR/ CEILING ASSEMBLY OF THE 1ST
 FLOOR CEILING.
 THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2
 HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS
 SHOWING THE ASSEMBLY.
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS
 (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 & CEILINGS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 3G) 2ND REQUEST. THE PLANS SHOW A HATCHED AREA WHERE
 THE CEILINGS ARE DROPPED TO 7 FEET ABOVE THE FINISH
 FLOOR. THE PLAN STILL SHOWS A HATCHED AREA FOR IN THE
 BATHROOM BUT THE PLANS INDICATE ALSO A 8 FOOT FLAT
 CEILING HEIGHT. DISCREPANCY IN PLANS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3H) COMPLIED.
  
 3I) 2ND REQUEST. PLEASE NOTE THIS ARCHITECTURAL SHEET
 IS LABELED ELECTRICAL 1ST FLOOR PLAN. PLEASE CORRECT
 AND UPDATE THIS SHEET.
  
 3K) SHEET 3.5 THIS SHEET LIST THE SINGLE FAMILY HOUSE
 AS A R1 OCCUPANCY. 2014 FBC-B 310.5.
  
 4A) 2ND REQUEST. SHEET A-3.2 2ND STORY FLOOR PLAN OF
 THE R2 APARTMENT BUILDING. HAS THE SAME ISSUES AS THE
 1ST FLOOR LAYOUT. SEE COMMENTS 3D-3H.
  
 4B) 2ND FLOOR. SHEET A3.2 THE 2ND FLOOR PORCH THE
 WINDOWS IN UNIT # 5 BEDROOM # 5 & THE LIVING ROOM ARE
 NOT IDENTIFIED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. NOTE THESE WINDOWS WILL HAVE TO BE SAFETY
 WINDOWS AS WELL LOCATED IN A HAZARDOUS LOCATION.
 2014 FBC-B 2406.4 HAZARDOUS LOCATIONS.
 THE LOCATIONS SPECIFIED IN SECTIONS 2406.4.1 THROUGH
 2406.4.7 SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS.
  
 5) 2ND REQUEST. THE 2ND STORY FLOOR SYSTEM DOES NOT
 PROVIDE HOW COMPLIANCE WITH STRUCTURE BORNE SOUND WILL
 BE ACHIEVED, SHOW COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5C) 2ND FLOOR. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 6) 2ND REQUEST, PLEASE PROVIDE COMPLIANCE WITH: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 7) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030064
 ADD: 513 SAPODILLA
 CONT: NUJAK CONSTRUCTION
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JUNE 02/ 2016
 ACTION: DENIED
  
 HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE
  
 PLEASE READ!!!!!!!!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY OLD AND OR VOIDED
 SHEETS & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) SHEET A3.3
 1A) 2ND REQUEST. IT APPEARS THE WIDTH AND HEIGHT
 DIMENSIONS OF THE WINDOW WERE REVERSED COMPARED TO THAT
 OF THE R2 APARTMENT BUILDING. 2014 FBC-R 310.1.1-3.
  
 1B) 2ND REQUEST. PLEASE SHOW WHAT THE SILL HEIGHT WILL
 BE FOR THE WINDOWS WITHIN BOTH BATHROOMS AND COMPLIANCE
 WITH
 R308.4.5.
  
 1C) 2ND REQUEST. SHEET S-2.3SF THE DEMO PLAN THERE ARE
 NO WALLS BEING DEMO-ED BETWEEN THE LIVING ROOM AND THE
 DINING ROOM. SHEET A3.3 IT IS NOT CLEAR IF A NEW WALL
 IS TO BE BUILT BETWEEN THESE ROOMS OR IF A HEADER IS
 BEING INSTALLED. NOTE THIS WILL BLOCK OFF ACCESS TO THE
 REMAINDER OF THE RESIDENCE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) 2ND REQUEST. THE FRONT AND REAR DOORS ARE BEING
 REPLACED BUT THE WIDTH OF THE DOOR IS UNKNOWN IN THE
 DOOR SCHEDULE. PLEASE SHOW COMPLIANCE WITH R3.11.2.
  
 1E) 2ND REQUEST. CODE SUMMARY ON THIS SHEET LIST A LOT
 OF CODE SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT
 CODE THESE SECTIONS WERE TAKEN FROM, NOT FOUND IN THE
 2014 FBC-EXISTING BUILDING CODE NOR THE 2014 FLORIDA
 RESIDENTIAL CODE. PLEASE NOTE ALL CODE REFERENCES,
 TABLE 503, TABLE 602 AND CHAPTER 7 ARE ALL REFERENCES
 TO THE FBC-BUILDING THE COMMERCIAL CODE. THIS IS A
 STAND ALONE SINGLE FAMILY DWELLING WHICH SHOULD BE
 REVIEWED UNDER THE 2014 FBC-RESIDENTIAL CODE.
  
 2) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE.
  
 3) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) 2ND REQUEST, WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  