| Plan Review Notes For Permit 16030064 |
| Permit Number |
16030064 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-08 11:31:28 | PLAN DENIED | | | | | | 1) DOOR SCHEDULE SHOWS AIR HANDLER CLOSET DOOR WOOD. | | | REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S 2014 | | | FBC (M) | | | 2) REFER TO SECTION 601.5 BALANCED RETURN AIR 2014 FBC | | | (M) | | | 3) PROVIDE DUCT SIZE ON THE PLAN. PER SECTION 107 FBC | | | 2014 | | | 4) PROVIDE EQUIPMENT SCHEDULE ON PLAN 107 FBC 2014. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|