| 2016-03-09 09:58:07 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. PLEASE PROVIDE SERVICE LOAD CALCULATION TO VERIFY |
| | SERVICE CONDUCTORS SELECTED AND SHOWN AT 2/0 CU. NEC |
| | 310.15B16 |
| | 2. LABEL MAINS 1 OF 6, 2 OF 6 ETC. PER NEC 230.71 |
| | 3. PROVIDE SIGNAGE TO INDICATE MULTIPLE SERVICES TO |
| | PROPERTY. SERVICE 1 OF 2 AND 2 OF 2 PER NEC 230.2E NOTE |
| | FOR FIRST RESPONDERS. |
| | 4. VERIFY SIZE OF GROUNDING ELECTRODE CONDUCTOR WHEN |
| | SERVICE CALCULATION IS PROVIDED. NEC 250.66. |
| | 5. CLARIFY EXTERIOR EMERGENCY LIGHTING SOURCE OF POWER, |
| | IS THERE A HOUSE PANEL FOR BUILDING EXTERIOR. CLARIFY |
| | MEANS OF AUTOMATIC CONTROLS PER FBC ENERGY CONSERVATION |
| | CODE 2014 5TH EDITION FOR ALL EXTERIOR LIGHTING. FBC EC |
| | 405.2 |
| | 6. PLEASE UPDATE ALL REFERENCES TO REFLECT CURRENT |
| | BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FAMILY, NEC 2011. |
| | 7. GRADE LEVEL UNITS TO BE PROVIDED WITH RECEPTACLE |
| | OUTLET PER NEC 210.52E2 |
| | 8. UNITS SHOWN ON SHEET E-1.3 ADDRESS WALL SPACING IN |
| | BED #5 WALL SPACE, NEC 210.52A2 |
| | 9. BATHROOM 1 AND 2 RECEPTACLES TO BE LABELED GFCI. NEC |
| | 210.8A1 |
| | 10. ADD A RECEPTACLE OUTLET TO UNIT #5 BATHROOM TO BE |
| | GFCI PROTECTED NEC 210.8A1 |
| | 11. ADDESS FIRE COMMENTS RELATED TO ELECTRICAL |
| | INSTALLATION FBC 107.3.5 |
| | 12. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL |
| | FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD |
| | YOU HAVE ANY QUESTIONS OR CONCERNS. |
| | |
| | |
| | |