2016-03-09 09:58:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE SERVICE LOAD CALCULATION TO VERIFY
 SERVICE CONDUCTORS SELECTED AND SHOWN AT 2/0 CU. NEC
 310.15B16
 2. LABEL MAINS 1 OF 6, 2 OF 6 ETC. PER NEC 230.71
 3. PROVIDE SIGNAGE TO INDICATE MULTIPLE SERVICES TO
 PROPERTY. SERVICE 1 OF 2 AND 2 OF 2 PER NEC 230.2E NOTE
 FOR FIRST RESPONDERS.
 4. VERIFY SIZE OF GROUNDING ELECTRODE CONDUCTOR WHEN
 SERVICE CALCULATION IS PROVIDED. NEC 250.66.
 5. CLARIFY EXTERIOR EMERGENCY LIGHTING SOURCE OF POWER,
 IS THERE A HOUSE PANEL FOR BUILDING EXTERIOR. CLARIFY
 MEANS OF AUTOMATIC CONTROLS PER FBC ENERGY CONSERVATION
 CODE 2014 5TH EDITION FOR ALL EXTERIOR LIGHTING. FBC EC
 405.2
 6. PLEASE UPDATE ALL REFERENCES TO REFLECT CURRENT
 BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION
 FAMILY, NEC 2011.
 7. GRADE LEVEL UNITS TO BE PROVIDED WITH RECEPTACLE
 OUTLET PER NEC 210.52E2
 8. UNITS SHOWN ON SHEET E-1.3 ADDRESS WALL SPACING IN
 BED #5 WALL SPACE, NEC 210.52A2
 9. BATHROOM 1 AND 2 RECEPTACLES TO BE LABELED GFCI. NEC
 210.8A1
 10. ADD A RECEPTACLE OUTLET TO UNIT #5 BATHROOM TO BE
 GFCI PROTECTED NEC 210.8A1
 11. ADDESS FIRE COMMENTS RELATED TO ELECTRICAL
 INSTALLATION FBC 107.3.5
 12. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  