| 2016-03-18 10:35:57 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 18/ 2016 |
| | ACTION: DENIED |
| | 6 UNIT/ R2 / APARTMENT BUILDING |
| | 1) THE CONTRACTOR NEEDS TO SPLIT THIS PERMIT PACKAGE |
| | INTO (2) SEPARATE PERMITS AND PLANS SINCE THERE ARE (2) |
| | TYPES OF BUILDINGS BEING RENOVATED. A COMMERCIAL |
| | APARTMENT BUILDING ( COMMERCIAL REMODEL) AND A SINGLE |
| | FAMILY DWELLING( RESIDENTIAL REMODEL) UNLESS THERE IS A |
| | USE THAT HAS NOT BEEN DECLARED SUCH AS A SOBER HOME, |
| | HALF-WAY HOUSE, ETC... NOTE THERE ARE (2) DIFFERENT |
| | OCCUPANCY TYPE R2 & R3 AND NEED TO BE REVIEWED UNDER |
| | THEIR APPROPRIATE CODES (FBC-BUILDING & |
| | FBC-RESIDENTIAL) AS WELL AS FOR INSPECTION PURPOSE AND |
| | FOR RECORD KEEPING . |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1.4 QUALITY OF BUILDING PLANS. . |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. |
| | |
| | 2) THE COVER-SHEET A-0.0 UNDER THE HEADING PROJECT |
| | DATA; |
| | 2A) UNDER THE WIND DESIGN THE PLANS ONLY LIST THE R2 |
| | OCCUPANCY NOT THE R3 SINGLE FAMILY UNIT. PLANS AND |
| | DESIGN CRITERIA NEED TO BE SPLIT INTO 2 PERMITS AND |
| | PACKAGES SO EACH BUILDING AND ASSOCIATED OCCUPANCY CAN |
| | BE REVIEWED UNDER THE APPROPRIATE CODE. 107,2,1,4, |
| | |
| | 2B) THE PROJECT DATA SHEET INDICATES THIS IS A LEVEL II |
| | ALTERATION. IT APPEARS MORE LIKE A LEVEL II LIMITED |
| | ALTERATION.2014 FBC-EXIST. BLDG. CODE 505.1 SCOPE. |
| | LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS |
| | 50 PERCENT OF THE AGGREGATE AREA OF THE BUILDING. THIS |
| | REVIEW WILL BE TREATED AS SUCH, PLEASE UPDATE PLANS. |
| | |
| | 2C) UNDER THE HEADING PROJECT DATA THERE ARE (2) CODES |
| | THAT ARE MISSING IN THE DESIGN CRITERIA, FOR THE |
| | COMMERCIAL 6 UNIT APARTMENT BUILDING THE 2014 |
| | FBC-BUILDING, AND FOR THE SINGLE FAMILY DWELLING UNIT |
| | THE 2014 FBC-RESIDENTIAL CODE, 2 SEPARATE AND DISTINCT |
| | CODES. THE RESIDENTIAL CODE DEALS STRICTLY WITH 1-2 |
| | FAMILY DWELLING UNITS!!!!!!!!!! SEE SCOPING AND TITLE |
| | REQUIREMENTS IN EACH CODE. 101.1 TITLE/ SCOPE 101.2.. |
| | |
| | 2D) UNDER THE HEADING APARTMENT BUILDING SCOPE OF WORK |
| | THE PLANS INDICATE THIS IS A 6 STORY BUILDING. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2E) THE PLANS DO NOT DECLARE IF THIS BUILDING IS FIRE |
| | SPRINKLERED OR NOT. IF FIRE SPRINKLERED WHAT TYPE OF |
| | FIRE SPRINKLER IS DESIGN? 107.3.5.1.1 MINIMUM PLAN |
| | REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. |
| | |
| | 2F) UNDER THE HEADING SINGLE FAMILY RESIDENCE THE PLANS |
| | INDICATE A 1 STORY HISTORIC BUILDING WHERE AS THE PLANS |
| | INDICATE A 2 STORY BUILDING. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 2G) THE TITLEBLOCK FOR ALL SHEETS HAS THE PRINTED NAME |
| | CROSSED OUT THAT WASN?T THE NAME OF THE ARCHITECT |
| | SEALING THE PLANS. ADMINISTRATIVE CODE 61G-16.004 (6) A |
| | SPACE REQUIRED FOR THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT. |
| | |
| | 3) SHEETS A-1.2, A-2.1, A-3.1, A-3.2, & A-3.3 ALL |
| | INDICATE THE PLANS WERE DESIGNED TO THE 2012 FLORIDA |
| | BUILDING CODE. PLEASE NOTE THE 2014 FLORIDA BUILDING |
| | CODE, 5TH EDITION WAS ADOPTED STATEWIDE ON JUNE 30/ |
| | 2015. PLEASE CORRECT PLANS. |
| | |
| | SHEET A-3.1 / 1ST FLOOR PLAN OF THE 2 STORY R2 |
| | APARTMENT BUILDING. |
| | 3A) THE DESIGNER OF RECORD HAS DECLARED THIS BUILDING |
| | TYPE AS A I-B BUILDING TYPE OF CONSTRUCTION. PLEASE |
| | NOTE ALL TRUSSES AND ROOF SHEATHING HAD TO BE INSTALLED |
| | WITH FIRE RETARDANT TREATED PLYWOOD. ALL NEW FRAMING |
| | MEMBERS AND ROOF SHEATHING WILL NEED TO COMPLY WITH |
| | FBC-B 603.1.1.3. 1. FIRE-RETARDANT-TREATED WOOD SHALL |
| | BE PERMITTED IN: 1.3. ROOF CONSTRUCTION, INCLUDING |
| | GIRDERS, TRUSSES, FRAMING AND DECKING. |
| | |
| | 3B) CODE SUMMARY ON THIS SHEET LIST A LOT OF CODE |
| | SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT CODE THESE |
| | SECTIONS WERE TAKEN FROM, NOT FOUND IN THE 2014 |
| | FBC-EXISTING BUILDING CODE NOR THE 2014 FBC-BUILDING |
| | CODE. |
| | |
| | 3C) DETAIL 1/ A-4 OF SHEET A-3.1 REFERENCES THE SFBC |
| | ITEM # 79 SECT. 37B. PLEASE UPDATE PLANS TO THE CURRENT |
| | 2014 FBC-B AND CURRENT CODE SECTIONS FOR TENANT |
| | SEPARATION REQUIREMENTS FOR TENANT SEPARATION WALLS. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING |
| | UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING |
| | UNITS IN THE SAME BUILDING AND WALLS SEPARATING |
| | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| | CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 708. |
| | |
| | |
| | 3D) IN UNIT # 2 THE WINDOWS IN THE BEDROOM #1, BATHROOM |
| | & KITCHEN ARE NOT IDENTIFIED. NOR ARE THE WINDOWS IN |
| | THE WINDOW SCHEDULE D-G NOT IDENTIFIED AS TO SIZE AND |
| | TYPE OF WINDOW. THE WINDOW SCHEDULE DOES NOT EVEN |
| | IDENTIFY THERE IS A WINDOW TYPE H LOCATED ON THE PLANS. |
| | |
| | 3E) PLEASE PROVIDE WHAT THE SILL HEIGHT OF THE WINDOW |
| | IS LOCATED IN THE BATHROOMS, PLEASE SHOW COMPLIANCE |
| | WITH FBC-B 2406.4.5. |
| | |
| | 3F) THE PLANS DO NOT INDICATE A CUT SECTION THROUGH THE |
| | FLOOR/ CEILING ASSEMBLY OF THE 1ST FLOOR CEILING. |
| | THE PLANS INDICATE THE DESIGNER OF RECORD REQUIRES A 2 |
| | HOUR RATING OF THIS ASSEMBLY BUT THERE ARE NO DETAILS |
| | SHOWING THE ASSEMBLY. |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS |
| | (4) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | & CEILINGS |
| | FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES |
| | SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR |
| | SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO |
| | THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS |
| | HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711. |
| | |
| | 3G) THE PLANS SHOW A HATCHED AREA WHERE THE CEILINGS |
| | ARE DROPPED TO 7 FEET ABOVE THE FINISH FLOOR. THE PLAN |
| | STILL SHOWS A HATCHED AREA FOR IN THE BATHROOM BUT THE |
| | PLANS INDICATE ALSO A 8 FOOT FLAT CEILING HEIGHT. |
| | DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 3H) THE CLOSET WHERE THE A/C AIR HANDLER SITS DOORS 4 & |
| | 13 ARE INDICATED AS A FULL LOUVER BUT DOES NOT INDICATE |
| | IF THIS DOOR IS WOOD OR METAL LOUVER DOOR. 2014 FBC-M |
| | 602.2.1. |
| | |
| | 3I) PLEASE NOTE THIS ARCHITECTURAL SHEET IS LABELED |
| | ELECTRICAL 1ST FLOOR PLAN. PLEASE CORRECT AND UPDATE |
| | THIS SHEET. |
| | |
| | 4) SHEET A-3.2 2ND STORY FLOOR PLAN OF THE R2 APARTMENT |
| | BUILDING. HAS THE SAME ISSUES AS THE 1ST FLOOR LAYOUT. |
| | SEE COMMENTS 3D-3H. |
| | |
| | 4A) INDICATES HOW THE |
| | |
| | 5) THE 2ND STORY FLOOR SYSTEM DOES NOT PROVIDE HOW |
| | COMPLIANCE WITH STRUCTURE BORNE SOUND WILL BE ACHIEVED, |
| | SHOW COMPLIANCE WITH: |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 5A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 5B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 5C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | NOTE: FOR TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 |
| | 720.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | 6) PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | 7) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030064 |
| | ADD: 513 SAPODILLA |
| | CONT: NUJAK CONSTRUCTION |
| | TEL: 561-320-2566 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 18/ 2016 |
| | ACTION: DENIED |
| | |
| | HISTORIC 2 STORY R-3 SINGLE FAMILY RESIDENCE |
| | |
| | 1) SHEET A3.3 |
| | 1A) IT APPEARS THE WIDTH AND HEIGHT DIMENSIONS OF THE |
| | WINDOW WERE REVERSED COMPARED TO THAT OF THE R2 |
| | APARTMENT BUILDING. 2014 FBC-R 310.1.1-3. |
| | |
| | 1B) PLEASE SHOW WHAT THE SILL HEIGHT WILL BE FOR THE |
| | WINDOWS WITHIN BOTH BATHROOMS AND COMPLIANCE WITH |
| | R308.4.5. |
| | |
| | 1C) SHEET S-2.3SF THE DEMO PLAN THERE ARE NO WALLS |
| | BEING DEMO-ED BETWEEN THE LIVING ROOM AND THE DINING |
| | ROOM. SHEET A3.3 IT IS NOT CLEAR IF A NEW WALL IS TO BE |
| | BUILT BETWEEN THESE ROOMS OR IF A HEADER IS BEING |
| | INSTALLED. NOTE THIS WILL BLOCK OFF ACCESS TO THE |
| | REMAINDER OF THE RESIDENCE. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1D) THE FRONT AND REAR DOORS ARE BEING REPLACED BUT THE |
| | WIDTH OF THE DOOR IS UNKNOWN IN THE DOOR SCHEDULE. |
| | PLEASE SHOW COMPLIANCE WITH R3.11.2. |
| | |
| | 1E) CODE SUMMARY ON THIS SHEET LIST A LOT OF CODE |
| | SECTIONS 705.4.3, 708.3 PLEASE INDICATE WHAT CODE THESE |
| | SECTIONS WERE TAKEN FROM, NOT FOUND IN THE 2014 |
| | FBC-EXISTING BUILDING CODE NOR THE 2014 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 2) PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE |
| | OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. |
| | |
| | 3) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |