Text |
| 2016-03-07 12:09:20 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | REVISION 11 |
| | SHEETS A0.1.4, A2.1.2, A2.1.7 |
| | |
| | 1. FBC 107, SHEET A0.1.4, THE SMALL STORAGE ROOM WAS |
| | REMOVED, BUT THE ENTIRE AREA IS NOW MARKED AS STORAGE. |
| | THIS IS SPECIFICALLY PROHIBITED BY FBC 1014.2(4). |
| | REVISE ROOM DESIGNATION. |
| | |
| | 2. FBC 107, REVISE SHEET A2.1.7 (7TH LEVEL FLOOR PLAN) |
| | TO BE CONSISTENT WITH SHEET A01.1.4 (7TH LEVEL LIFE |
| | SAFETY PLAN). BOTH PAGES WERE INCLUDED IN THIS REVISION |
| | BUT THE STORAGE ROOM REMOVED ON SHEET A2.1.7 STILL |
| | REMAINS ON SHEET A2.1.7; PLEASE CORRELATE. |
| | |
| | 3. FBC TABLE 1004.1.1, THE OCCUPANT LOAD FOR THE DECK |
| | (50 SF/OCCUPANT) ON SHEET A0.1.4 DOES NOT APPEAR TO |
| | COMPLY WITH FBC TABLE 1004.1.1. SWIMMING POOL DECK |
| | REQUIRES 30 SF GROSS, DECKS REQUIRE 15 SF GROSS. REVISE |
| | OCCUPANT LOAD ACCORDINGLY, OR PROVIDE A LETTER TO THE |
| | BUILDING OFFICIAL REQUESTING USE OF DESIGN OCCUPANT |
| | LOAD AS PER FBC 1004.1.1 EXCEPTION. IF 30 SF GROSS IS |
| | USED FOR OCCUPANT LOAD RATHER THAN 15 SF, PROVIDE A |
| | LETTER TO THE BUILDING OFFICIAL REQUESTING USE OF |
| | SWIMMING POOL DECK OCCUPANT LOAD RATHER THAN DECK |
| | OCCUPANT LOAD ALONG WITH RATIONALE. |
| | |
| | 4. FBC 107, SHEET A0.1.4, REVISED OCCUPANT LOAD (114) |
| | IS NOT CONSISTENT WITH EGRESS CAPACITY CALCULATIONS |
| | (98). SEE ALSO COMMENT #3 AND CORRELATE. |
| | |
| | IF A LETTER IS SUBMITTED, PLEASE SEND VIA EMAIL PRIOR |
| | TO RESUBMITTAL FOR PRELIMINARY BUILDING OFFICIAL |
| | APPROVAL. |
| | |
| | 5. A PREVIOUS CORRECTION LIST REQUESTED THAT ARCHITECT |
| | CONFIRM FIELD CONDITIONS. ARCHITECT'S RESPONSE WAS THAT |
| | THIS IS NOT A PART OF THEIR AGREEMENT WITH THE OWNER. |
| | PLEASE NOTE THAT IT IS MY UNDERSTANDING THAT A |
| | MECHANICAL ROOM, 2ND FLOOR AMENITY AREA IS DEPICTED ON |
| | SHEET A2.1.2 AS OPEN, BUT A SLAB WAS INSTALLED IN THIS |
| | LOCATION. PLAN REVIEW WILL PASS WITHOUT THIS BEING |
| | CORRECTED ON THE PLAN, BUT IT IS POSSIBLE THAT |
| | INSPECTIONS WILL FAIL UNLESS THE AS BUILT CONDITION IS |
| | CONSISTENT WITH THE PLAN. IT IS RECOMMENDED THAT THIS |
| | CHANGE BE INCORPORATED INTO THIS AS-BUILT DRAWING; |
| | PLEASE COORDINATE WITH CONTRACTOR. |
| | |
| | 6. NA |
| | |
| | 7. WHEN RESUBMITTING, PLEASE PROVIDE THREE SETS AS |
| | REQUIRED FOR THRESHOLD JOBS, FS 553, FBC 107. ONE SET |
| | IS REQUIRED FOR EACH OF THE FOLLOWING PARTIES: 1. |
| | CONTRACTOR, 2. SPECIAL INSPECTOR, 3. CITY RECORD SET. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |