| Date |
Text |
| 2016-05-14 12:26:53 | ****PROVISOS**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ***REVISED 6/23/16; ADDED RE-PLAT TO PROVISO #2 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FBC 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL |
| | OF THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| | CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A |
| | BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| | FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| | SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| | OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| | AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION |
| | AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL |
| | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| | |
| | 2. A UNITY OF TITLE OR RE-PLAT IS REQUIRED FOR |
| | COMPLIANCE WITH FBC 705.8. WHEN AVAILABLE, PROVIDE THE |
| | BOOK AND PAGE WHERE THIS HAS BEEN RECORDED OR PROVIDE A |
| | COPY OF THE RECORDED UNITY OF TITLE OR RE-PLAT |
| | (REQUIRED PRIOR TO C.O.). |
| | |
| | 3. REVISION REQUIRED: |
| | A. PROVIDE REVISED SHEET A100. |
| | B. THE WIND TUNNEL REPORT SUBMITTED IS NOT SIGNED AND |
| | SEALED AND IS AN "INTERIM" REPORT RATHER THAN THE |
| | "FINAL STRUCTURAL LOADS REPORT." PROVIDE THE DIGITALLY |
| | SIGNED AND SEALED FINAL STRUCTURAL LOADS REPORT. |
| | |
| | 4. PER DOR, NV5 HAS REVIEWED THE FOUNDATION DESIGN PER |
| | THEIR RECOMMENDATION AND WILL MONITOR THE AUGERCAST |
| | PILE INSTALLATION. |
| | |
| | |
| | |