| Plan Review Notes For Permit 16030058 |
| Permit Number |
16030058 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-04 11:08:12 | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE SANITARY RISER WITH-ALL STACKS | | | LABELED TO MATCH FLOOR PLAN-INCLUDE DFU FOR ALL STACKS. | | | PER WPB AMEND. TO FBC SEC. 107.3.5.1.3(13) | | | | | | 2.LABEL ALL STACKS ON FLOOR PLAN TO MATCH RISER. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 3.SHOW ALL UNDERGROUND WATER PIPING. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 4. SHTS. P-301-A AND P-301-B ARE MARKED FOR REFERENCE | | | ONLY PLEASE SUBMIT SHEETS FOR PERMIT REVIEW AND | | | CONSTRUCTION. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 5. PROVIDE STORM RISER DIAGRAM WITH SQ FT. DRAINED-ON | | | EACH LEADER. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 6. PROVIDE CALCULATIONS FOR GREASE INTER . IF GREASE | | | INTERCEPTOR IS NOT BEING INSTALLED UNDER THIS PERMIT | | | PLEASE NOT ON PLAN | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 7. ARE BATHROOMS ON GROUND FLOOR GOING IN UNDER THIS | | | PERMIT. PLEASE PROVIDE RISER DIAGRAM. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 8; PLEASE PROVIDE CLEAR SCOPE OF PLUMBING WORK UNDER | | | THIS PERMIT. | | | PER WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | | | | DO TO PLANS BEING INCOMPLETE OR UNCLEAR, A | | | COMPREHENSIVE PLAN REVIEW CANNOT BE DONE AT THIS TIME, | | | THERE MAYBE ADDITIONAL COMMENTS ON RESUBMITTAL OF | | | PLANS. | | | | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|