| 2016-03-31 12:37:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1. SHEET 0103 C301 AAF TOD - ONLY ONE (1) WATER SUPPLY |
| | WAS NOTED ON THE DRAWING. |
| | |
| | NFPA 1, 18.3 WATER SUPPLIES. |
| | 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING |
| | THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE |
| | PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, |
| | BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER |
| | CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE |
| | APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH |
| | SECTION 18.4. |
| | |
| | NFPA 101, 1.8 FLORIDA FIRE PREVENTION CODE AND FLORIDA |
| | BUILDING CODE INTERRELATION. THE FLORIDA FIRE |
| | PREVENTION CODE CONTAINS SEVERAL PROVISIONS AND |
| | REQUIREMENTS THAT MAY INTERRELATE WITH THE FLORIDA |
| | BUILDING CODE. IT IS NOT THE INTENT OF THIS CODE THAT |
| | SUCH INTERRELATION RESULT IN DUPLICATE REVIEWS AND |
| | INSPECTIONS BY EITHER THE FIRESAFETYAUTHORITY OR THE |
| | BUILDING OFFICIAL. THE AUTHORITY HAVING JURISDICTION |
| | OVER FIRESAFETY IS RESPONSIBLE FOR ENFORCEMENT OF THE |
| | FLORIDA FIRE PREVENTION CODE HEREOF, AND, IN THE EVENT |
| | THAT A DISPUTE ARISES REGARDING THE ENFORCEMENT OF THE |
| | FLORIDA FIRE PREVENTION CODE AS RELATED TO THE |
| | ENFORCEMENT OF THE FLORIDA BUILDING CODE, THE AUTHORITY |
| | HAVING JURISDICTION OVER FIRESAFETY SHALL RESOLVE THE |
| | DISPUTE BY THE PROCEDURE SET FORTH IN CHAPTER 633 AND |
| | CHAPTER 553, FLORIDA STATUTES, AS REQUIRED BY SECTION |
| | 633.104(5), FLORIDA STATUTES. |
| | |
| | PER FL BLDG CODE 5TH ED. SECTION 403 HIGH-RISE |
| | BUILDINGS |
| | 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS. REQUIRED |
| | FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO NO FEWER |
| | THAN TWO WATER MAINS LOCATED IN DIFFERENT STREETS. |
| | SEPARATE SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH |
| | CONNECTION TO THE WATER MAIN AND THE PUMPS. EACH |
| | CONNECTION AND THE SUPPLY PIPING BETWEEN THE CONNECTION |
| | AND THE PUMPS SHALL BE SIZED TO SUPPLY THE FLOW AND |
| | PRESSURE REQUIRED FOR THE PUMPS TO OPERATE. |
| | |
| | PLEASE PROVIDE FOR TWO (2) SEPARATE WATER SUPPLIES. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |