| 2016-03-08 03:33:04 | 1) THE SUBMITTED PLANS ARE TYPICAL FOR A SWIMMING POOL | | | AND THERE ARE NO SECTIONS, DETAILS ETC. FOR THE | | | FOUNTAIN. SUBMIT DRAWINGS THAT REFLECT THE SCOPE OF THE | | | WORK TO BE DONE.FBC 107.2.1. | | | 2) THE PIPING DIAGRAM IS FOR A SWIMMING POOL. SUBMIT A | | | PIPING DIAGRAM FOR THE FOUNTAIN PIPING. | | | 3) DELETE ALL DETAILS FROM THE PLAN THAT DO NOT APPLY | | | TO THIS INSTALLATION. FBC 107.2.1. | | | COMMENTS UPDATED ON 3/24/16. | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|