2016-03-10 13:17:52INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RESIDENTIAL BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE ALL APPLICABLE CODES TO REFLECT NEW
 FBC 2014 5TH EDITION SET AND NFPA 70 NEC 2011. SEE
 SHEET E.1 GENERAL NOTES AND ENERGY EFFICIENCY CODES ARE
 OUTDATED.
 2. ADD RECEPTACLE OUTLETS TO COMPLY WITH WALL SPACING
 IN BEDROOM 1 AND 2. FBC RES E3901.2.2
  
  
  