| 2016-04-25 17:09:09 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030035 | | | 4/25/16 | | | | | | 1) THE NEW AC PLAN SHOWS 5" DIAMETER FLEX DUCTS | | | CONNECTING TO NEW 4X4 DIFFUSERS- PLEASE CLARIFY HOW THE | | | 5" WILL CONNECT TO THE 4" COLLAR AND PROVIDE AN AIR | | | DEVICE SCHEDULE ON THE PLANS. | | | 2) THE VENTILATION CALCULATIONS ARE NOT IN COMPLIANCE | | | WITH TABLE 403.3 WHICH REQUIRES OFFICE SPACES TO BE | | | CALCULATED USING AN OCCUPANT DENSITY OF 5 PERSONS PER | | | SF. AND LOBBIES AT 10 PERSONS PER SF. THE VENTILATION | | | IS THEN CALCULATED AT 5CFMS PER PERSON + .06 CFMS PER | | | SF. | | | 3) PLEASE SHOW ALL DUCT ALTERATIONS IN THE NEW LOBBY | | | AND OPEN OFFICE ROOMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|