2016-04-25 17:09:092ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030035
 4/25/16
  
 1) THE NEW AC PLAN SHOWS 5" DIAMETER FLEX DUCTS
 CONNECTING TO NEW 4X4 DIFFUSERS- PLEASE CLARIFY HOW THE
 5" WILL CONNECT TO THE 4" COLLAR AND PROVIDE AN AIR
 DEVICE SCHEDULE ON THE PLANS.
 2) THE VENTILATION CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH REQUIRES OFFICE SPACES TO BE
 CALCULATED USING AN OCCUPANT DENSITY OF 5 PERSONS PER
 SF. AND LOBBIES AT 10 PERSONS PER SF. THE VENTILATION
 IS THEN CALCULATED AT 5CFMS PER PERSON + .06 CFMS PER
 SF.
 3) PLEASE SHOW ALL DUCT ALTERATIONS IN THE NEW LOBBY
 AND OPEN OFFICE ROOMS.
  