| 2016-03-10 15:53:21 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16030035 | | | 3/10/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING: | | | ALTERED EXISTING SYSTEMS. | | | "IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | | PROCEDURE OF ASHRAE 62." PLEASE PROVIDE A VENTILATION | | | CALCULATION IN ACCORDANCE WITH TABLE 403.3 FBC-14 | | | MECHANICAL. | | | 2) THE PLAN IS IN COMPLETE: SOME DUCT SIZES NOT SHOWN, | | | DUCT TYPES NOT IDENTIFIED, CFM'S AT DIFFUSERS AND | | | RETURNS NOT SHOWN, RETURN GRILLS AT BACK ROOMS OF | | | OFFICES 3 & 4 NOT SHOWN. | | | 3) PLEASE CLARIFY IF THIS IS A PLENUM CEILING: PROVIDE | | | A NOTE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|