| Date |
Text |
| 2016-03-08 11:04:11 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1.PLEASE DELETE FROM GENERAL NOTES ALL REFERENCES |
| | PERTAINING TO RESIDENTIAL INSTALLATIONS. |
| | 2.ADD GENERAL NOTES INDICATING NEC 410.130G |
| | REQUIREMENTS FOR FLORESCENT LUMINAIRES. |
| | 3.CLARIFY MEANS OF AUTOMATIC CONTROLS PER FBC ENERGY |
| | CONSERVATION CODE 2014 5TH EDITION FOR ALL LIGHTINGS. |
| | FBC EC 405.2 |
| | 4.CORRECT TYPO TO INDICATE NEC 2011 NOT NEC 2010. |
| | 5.SHOW LIGHTING AND POWER CIRCUIT DESIGNATION ON FLOOR |
| | PLAN. FBC 107.3.5 |
| | 6.SHOW PER NEC 700.12F THAT UNIT EQUIPMENT IS SERVED |
| | FROM THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCH. |
| | 7.CLARIFY EXISTING PANEL C VOLTAGE. IS IT A SINGLE |
| | PHASE 120/240? SHOWN AS 208/240. NOTE THAT SINGLE PHASE |
| | IS CALLED OUT BUT PHASE A, B, C 3/PHASE ARRANGEMENT IS |
| | SHOWN. REFLECT AN ACCURATE PANEL SCHEDULE FOR APPROVAL. |
| | FBC 107.3.5 |
| | 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE |
| | TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU |
| | HAVE ANY QUESTIONS OR CONCERNS. |
| | |
| | |
| | |