2016-03-08 11:04:11INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE DELETE FROM GENERAL NOTES ALL REFERENCES
 PERTAINING TO RESIDENTIAL INSTALLATIONS.
 2.ADD GENERAL NOTES INDICATING NEC 410.130G
 REQUIREMENTS FOR FLORESCENT LUMINAIRES.
 3.CLARIFY MEANS OF AUTOMATIC CONTROLS PER FBC ENERGY
 CONSERVATION CODE 2014 5TH EDITION FOR ALL LIGHTINGS.
 FBC EC 405.2
 4.CORRECT TYPO TO INDICATE NEC 2011 NOT NEC 2010.
 5.SHOW LIGHTING AND POWER CIRCUIT DESIGNATION ON FLOOR
 PLAN. FBC 107.3.5
 6.SHOW PER NEC 700.12F THAT UNIT EQUIPMENT IS SERVED
 FROM THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCH.
 7.CLARIFY EXISTING PANEL C VOLTAGE. IS IT A SINGLE
 PHASE 120/240? SHOWN AS 208/240. NOTE THAT SINGLE PHASE
 IS CALLED OUT BUT PHASE A, B, C 3/PHASE ARRANGEMENT IS
 SHOWN. REFLECT AN ACCURATE PANEL SCHEDULE FOR APPROVAL.
 FBC 107.3.5
 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  