Plan Review Notes
Plan Review Notes For Permit 16030030
Permit Number 16030030
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-09 14:19:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 PROVIDE ELECTRICAL DIAGRAM FOR PROPOSED SIGN WITH THE
 FOLLOWING INFORMATION ( WBA 107 INSUFFICIENT DOCUMENTS.
 )
  
 NEC 600.5 A DEDICATED 20 AMP BRANCH CIRCUIT THAT SUPPLY
 NO OTHER LOAD.
 NEC 600.6 A DISCONNECT SWITCH AT SIGN LOCATION ( WITHIN
 SIGHT. )
 C405.2.4 EXTERIOR LIGHTING CONTROLS
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS..
  