| Plan Review Notes For Permit 16030026 |
| Permit Number |
16030026 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-05-09 17:47:33 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030026 | | | 5/9/16 | | | | | | 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. PLEASE | | | RELOCATE THE 14X16 DUCT SHOWN ON TOP OF THE WALL | | | BETWEEN THE CLASSROOM AND MEDIA ARTS ROOM. | | | 2) SHEET M-1: IT APPEARS THAT THE THERMOSTAT FOR AHU-3 | | | IS MISLABELED AS AHU-2 BY THE 38X24 RETURN GRILL. | | | 3) M-3: THE FRESH AIR CALCULATION FOR THE MULTI-PURPOSE | | | ROOM MUST BE 7.5 CFM PER PERSON- TABLE 403.3. | | | 4) M-5: THE GRAVITY VENTILATOR DETAIL IS NOT LEGIBLE- | | | APPEARS TO BE A NEGATIVE IMAGE. PLEASE PROVIDE A CLEAR | | | DETAIL AND EQUIPMENT SCHEDULE. | | | 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS | | | OF ALL ROOFTOP EQUIPMENT AND CLEARANCE DISTANCE | | | MEASUREMENTS FOR ALL MECHANICAL AND GRAVITY AIR INTAKES | | | TO EXHAUST AND VENT OUTLETS- SECTION 401.4. | | | 6) M-5: THE UNIT DATA IN THE CONDENSING UNIT DETAIL | | | APPEARS NOT TO BE CONSISTENT WITH THE SIZES OF THE NEW | | | CU-2 & 3 WHICH APPEAR TO MUCH LARGER DIMENSIONALLY. | | | PLEASE PROVIDE SITE SPECIFIC DESIGN DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|