2016-05-09 17:47:332ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030026
 5/9/16
  
 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. PLEASE
 RELOCATE THE 14X16 DUCT SHOWN ON TOP OF THE WALL
 BETWEEN THE CLASSROOM AND MEDIA ARTS ROOM.
 2) SHEET M-1: IT APPEARS THAT THE THERMOSTAT FOR AHU-3
 IS MISLABELED AS AHU-2 BY THE 38X24 RETURN GRILL.
 3) M-3: THE FRESH AIR CALCULATION FOR THE MULTI-PURPOSE
 ROOM MUST BE 7.5 CFM PER PERSON- TABLE 403.3.
 4) M-5: THE GRAVITY VENTILATOR DETAIL IS NOT LEGIBLE-
 APPEARS TO BE A NEGATIVE IMAGE. PLEASE PROVIDE A CLEAR
 DETAIL AND EQUIPMENT SCHEDULE.
 5) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL ROOFTOP EQUIPMENT AND CLEARANCE DISTANCE
 MEASUREMENTS FOR ALL MECHANICAL AND GRAVITY AIR INTAKES
 TO EXHAUST AND VENT OUTLETS- SECTION 401.4.
 6) M-5: THE UNIT DATA IN THE CONDENSING UNIT DETAIL
 APPEARS NOT TO BE CONSISTENT WITH THE SIZES OF THE NEW
 CU-2 & 3 WHICH APPEAR TO MUCH LARGER DIMENSIONALLY.
 PLEASE PROVIDE SITE SPECIFIC DESIGN DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER