| 2016-05-13 15:05:44 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030026 |
| | ADD: 425 24TH ST. |
| | CONT: CLEAR SPAN STRUCTURES, LLC |
| | TEL: 561-803-8100 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. MAY 13/ 2016 |
| | ACTION: DENIED |
| | |
| | BUILDING TYPE; III-A (PROTECTED)/ SPRINKLERED. |
| | PLEASE NOTE SHEETS LS-1 & A1 SHOWS PHASE III WITH A |
| | CONTINUATION OF WORK FROM PHASE II COVERED UNDER PERMIT |
| | 12030123 (2007 FBC-B). UNDER THIS EDITION OF THE FBC |
| | CORRIDORS HAD TO BE FIRE RATING SO THE PHASE III PERMIT |
| | WILL CONTINUE THE 1 HOUR FIRE RATING OF THE NEW |
| | CORRIDORS. |
| | |
| | 1) SHEET A1: |
| | 1A-B) COMPLIED. |
| | |
| | 1C) SEMI- COMPLIED. PLEASE NOTE SHEET A1 VERSES SHEET |
| | M-1, SHEET M-1 SHOWS DUCT BEING PARALLEL TO THE COMMON |
| | WALL BETWEEN ROOM 302 & 305 AS DEPICTED THE WALL GOES |
| | DIRECTLY THROUGH THE CENTER OF THE DUCT SINCE THE WALL |
| | TYPE B1 GOES ALL THE WAY TO THE UNDERSIDE OF THE ROOF |
| | DECK. THIS APPEARS TO BE A DISCREPANCY IN THE PLANS |
| | WHERE THE MAIN TRUNK LINE NEEDS TO BE SHIFTED TO EITHER |
| | SIDE OF WALL TYPE B1. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED, EITHER |
| | WALL B1 DOES NOT CONTINUE TO THE ROOF DECK AND WILL |
| | NEED BRACING OR THE DUCT PLACEMENT NEEDS TO BE MOVED. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2) SHEET A2 SHOWS A SECTION THROUGH THE ROOF FOR THE |
| | CURB MOUNTED GRAVITY INTAKE VENTILATOR. PLEASE NOTE THE |
| | GRAVITY VENTILATOR WILL NEED TO SIT ON A CURB THAT IS |
| | MOUNTED TO THE ROOF FRAMING. THIS REVIEW NO CURB WAS |
| | SUBMITTED. PLEASE PROVIDE THE ATTACHMENT METHOD AND |
| | WIND DESIGN THAT SUPPORTS THE CURB AND GRAVITY |
| | VENTILATOR TO STAY IN PLACE IN A HIGH WIND EVENT. |
| | . 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| | STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| | DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| | INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| | COMPATIBILITY AND BOTH SHORT- AND LONG-TERM |
| | MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| | TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| | WIND LOADS? |
| | |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | |
| | 2A) SEMI-COMPLIED. , 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31) (D) ROOFING PRODUCTS AND ASSEMBLIES/ |
| | CURBS/ INTAKE AND ROOF TOP EXHAUST FANS. |
| | PLEASE PROVIDE THE CONNECTION FROM THE ROOF TOP CURB TO |
| | THE GRAVITY VENTILATOR. |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2B COMPLIED. . 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 2C) COMPLIED. PLEASE PROVIDE DETAILS FOR THE FRAMING |
| | REQUIRED AROUND THE NEW OPENING IN THE ROOF SYSTEM. |
| | THIS FRAMING SHOULD TIE BACK INTO THE MWFRS, (MAIN WIND |
| | FORCE RESISTING SYSTEM). |
| | |
| | 2D) SEE COMMENTS (2A-2C). FOR ALL ROOF TOP EQUIPMENT, |
| | CURBS & FANS DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| | DECK AS WELL AS FROM THE CURB AND ROOF TOP FAN. 2014 |
| | FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |