2016-03-10 15:10:231ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030026
 3/10/16
  
 1) SHEETS M-1 & M-2: A) FLEX DUCTS SHALL NOT PASS
 THROUGH THE FIRE-RATED CORRIDOR WALLS OR THE FIRE-RATED
 CLASSROOM 305/MEDIA ARTS 302 WALL.
 2) M1 & M2: THE 14X16 TRUNK FROM AHU-2 IS SHOWN ON THE
 PLAN TO BE LOCATED ON TOP OF A THE FIRE-RATED CLASSROOM
 305/MEDIA ARTS 302- PLEASE RELOCATE THE DUCT PER
 SECTION 607.5.3.
 3) M1 & M2: FIRE DAMPER MISSING AT THE 38X24 RETURN
 GRILL LOCATED IN THE FIRE-RATED BACK STAGE/PERFORMANCE
 AREA WALL- SECTION 607.5.3.
 4) M1 & M2: THE FIBERGLASS DUCTS PENETRATING THE
 FIRE-RATED CORRIDOR PARTITION ARE PERMITTED TO BE
 INSTALLED WITHOUT DAMPERS BUT REQUIRE STEEL SLEEVES PER
 SECTIONS 607.1.1 & 607.5.3 FBC-14 MECHANICAL.
 5) A-1.1 & M-2: THE SCOPE OF WORK OUTLINE ON A-1.1 DOES
 NOT INCLUDE THE STORAGE ROOM, HOWEVER AC IS BEING
 SUPPLIED TO IT ON M-2.
 6) M-1 & M-2: PLEASE PROVIDE NOTES #7 & 15 ON THE
 PLANS.
 7) M-2: THE PLAN INDICATES A TOTAL OF 4800 CFM RETURN
 AIR FROM THE PERFORMANCE AREA TO AHU-3, HOWEVER THE
 TOTAL SUPPLY AIR TO THE AREA IS 6280 CFM- PLEASE
 CLARIFY.
 8) THE ENERGY CONSERVATION FORM LISTS AHU/CU-1 & 2,
 HOWEVER THE PLAN IS INDICATING AHU/CU- 2 & 3- PLEASE
 CORRECT.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND MIAMI-DADE
 NOA'S FOR THE GREENHECK GRAVITY INTAKE VENTILATOR
 REVIEWED AND APPROVED WITH SIGNATURE BY THE EOR.
 10) PROVIDE A ROOF PLAN INDICATING THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS FROM THE AIR INTAKES TO
 EXHAUST AND VENT OUTLETS.
  