| 2016-03-07 17:11:11 | JOB PERMIT NUMBER: 16030026 |
| | JOB ADDRESS: 425 24TH STREET |
| | WEST PALM BEACH FLORIDA |
| | DATE: MARCH 7 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - FBC-B 1011. EXIT SIGNAGE REQUIRED. MISSING EXIT SIGNS |
| | BY DOUBLE DOORS IN THE FOLLOWING LOCATIONS MEDIA ARTS |
| | ROOM , CLASSROOM 305 , AND BACKSTAGE 313. FURTHERMORE |
| | AN EXIT SIGN IS MISSING IN SINGLE DOOR BY HALLWAY 3 |
| | LEADING TO HALLWAY 4. |
| | - FBC E C405.4 EXIT SIGNS SHALL NOT EXCEED 5 WATT PER |
| | SIDE 27. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL |
| | BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR |
| | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY |
| | BE ON OWN CIRCUIT. ( KEEP IN MIND WHEN ADDING EXIT |
| | SIGNS. ) |
| | - PLEASE ADD TO ELECTRICAL GENERAL NOTES NEC 300.21 |
| | OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR THROUGH |
| | FIRE-RESISTANT-RATED WALLS, PARTITIONS , FLOORS, OR |
| | CEILINGS SHALL BE FIRE STOPPED USING APPROVED METHODS |
| | TO MAINTAIN THE FIRE RESISTANCE RATING. NEC 300.7 A |
| | PROPERLY SEALING OF CONDUITS IS REQUIRED WHEN EXPOSED |
| | TO DIFFERENT TEMPERATURES. |
| | - PROVIDE ARC-FLASH HAZARD WARNING LABEL AND AVAILABLE |
| | FAULT CURRENT MARKING IN ACCORDANCE WITH NEC 110.16 , |
| | 110.24 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | |