| Plan Review Notes For Permit 16030024 |
| Permit Number |
16030024 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-02 06:07:36 | 1) THE GAS DRAWING REFERS TO A 10 PSI PRESSURE ON THE | | | LINE FROM THE TANK. THERE IS NO TABLE IN THE 2014 FUEL | | | GAS CODE FOR A 10 PSI SYSTEM. SUBMIT A COPY OF THE | | | SIZING TABLE BEING USED FOR THE 10 PSI PORTION OF THIS | | | SYSTEM. | | | 2) THE EXISTING BTU LOAD NOTED ON THE PLAN DOES NOT | | | INCLUDE THE POOL HEATER. CLARIFY. | | | 3) THE NEW BTU LOAD LISTED REFERS TO A RANGE BUT THE | | | DRAWING ALSO SHOWS A NEW GRILL. CLARIFY. | | | 4) THE DRAWING REFERS TO SIZING TABLE 402.4 (32). THIS | | | TABLE IS FOR CSST MATERIAL BUT THERE IS NO CSST SHOWN | | | ON THE DRAWING. CLARIFY. | | | 5) IS THE GRILL LOCATED UNDER A ROOF, AS ON A ROOFED | | | OVER PATIO? IF SO, A HOOD MAY BE REQUIRED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|