| Plan Review Notes For Permit 16030008 |
| Permit Number |
16030008 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-27 05:04:20 | 1) SHOW THE LOCATION OF THE CONTROLLER AND THE REQUIRED | | | RAIN SENSOR ON THE PLANS.FBC 107.2.1. | | | 2) A RAIN SENSOR IS REQUIRED ON THE SYSTEM PER FLA. | | | STATUTE 373.62. THE NOTE "NO RAIN SENSOR" WRITTEN ON | | | THE PLAN IS UNACCEPTABLE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|