| 2016-03-03 10:09:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF |
| | THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101, |
| | INCLUDING CHAPTER 43 BUILDING REHABILITATION, ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | 2. THE DUST PARTITION PROJECTS INTO A FIRE RATED |
| | CORRIDOR. PROVIDE FOR THE REQUIRED FIRE RATING IN THIS |
| | CORRIDOR. INDICATE THE LOCATION OF EXISTING FIRE |
| | SPRINKLER TO ENSURE REQUIRED COVERAGE AND THAT THEY |
| | WON'T BE BLOCKED. |
| | |
| | 3. PROVIDE THE FIRE RATING SPEC'S FOR FLOOR PLAN NOTE # |
| | 6. |
| | |
| | 4. PROVIDE AND INDICATE THE AREAS IN EACH ROOM OF FIRE |
| | RESISTNACE RATING PER THE FIRE RESISTANCE SCHEDULE. |
| | |
| | 5. PROVIDE THE LOCATION OF THE EXISTING FIRE ALARM |
| | DEVICES AND INDICATE IF THEY WILL BE REMOVED/REPLACED. |
| | |
| | 6. PROVIDE THE LOCATION OF THE EXISTING FIRE SPRINKLERS |
| | AND INDICATE IF THEY WILL BE REMOVED/REPLACED. |
| | |
| | 7. PROVIDE A NOTE INDICATING AND ENSURING THE |
| | FOLLOWING. |
| | |
| | A. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | |
| | B. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE |
| | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP |
| | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | C. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | |
| | |