2016-03-10 06:39:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030005
 ADD: 1309 N. FLAGLER DR. / 2ND FLOOR RENOVATION N.W.
 CORNER
 CONT: BMS CAT INC.
 TEL: 561-401-2522
 E-MAIL: ??????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 10/2016
 ACTION: DENIED
  
 1) SHEET A1.00 INDICATES IN NOTE 4 THE REMOVAL OF ALL
 FIRE INSULATION. DETAIL 3 OF THIS SHEET INDICATES THE
 INSTALLATION OF NEW FIRE PROOFING TO MATCH THE ORIGINAL
 SPECIFIED VALUES. THE PLANS INDICATE THIS BUILDING IS A
 BUILD. TYPE I-B WITH FIRE RATING OF:
 BEAMS / JOINTS 2 HR
 FLOOR/ CEILING 2 HR
 ROOF ROOF/CEILING 1HR
 SHAFT ENCLOSURES 2 HR
 2014 FBC-B TABLE 601
  
 2) DETAIL 3 & 4 BOTH SHOW THE USE OF CLOSED CELL SPRAY
 FOAM INSULATION. PLEASE PROVIDE THE TESTING REPORT FOR
 THIS PRODUCT. THIS REPORT SHALL PROVIDE ALLOWABLE USES,
 LIMITATIONS, ALLOWABLE THICKNES ON VERTICAL SURFACES,
 THERMAL RESISTANCE (R-VALUES). DETAIL # 4 SHOWS THE
 FOAM SPRAY INSULATION ABOVE THE CEILING WHERE THE
 DRYWALL DOES NOT CONTINUE TO THE DECK ABOVE. HOW WILL
 COMPLIANCE WITH SECTION 2603.4 OF THE 2014 FBC-B BE
 MET.
  
 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.10, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 1/2- INCH (12.7 MM) GYPSUM
 WALLBOARD OR A MATERIAL THAT IS TESTED IN ACCORDANCE
 WITH AND MEETS THE ACCEPTANCE CRITERIA OF BOTH THE
 TEMPERATURE TRANSMISSION FIRE TEST AND THE INTEGRITY
 FIRE TEST OF NFPA 275. COMBUSTIBLE CONCEALED SPACES
 SHALL COMPLY WITH SECTION 718.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION