| 2016-03-09 13:10:00 | REVIEW 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | |
| | |
| | - FOR A FULL HOUSE REWIRING REMODELING PROJECT FULL |
| | SIZE DRAWINGS SHALL BE SUBMITTED SIGN AND SEALED. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | - KEEP IN MIND THE FOLLOWING CODE SECTIONS THAT WILL |
| | APPLY. |
| | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. |
| | FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | SMOKE/CARBON ALARMS REQUIRED PER RESIDENTIAL CODE |
| | SECTIONS 314 & 315. |
| | NEC 404.2 C NUETRAL ( GROUNDED CONDUCTOR ) SHALL BE |
| | PROVIDED AT SWITCH LOCATION. |
| | NEC 250.94 PROVIDE INTERSYSTEM BONDING. {NOTE} I |
| | NOTICED THE GROUNDING ELECTRODE CONDUCTOR IS UNDERSIZED |
| | CHECK TABLE NEC 250.66 |