Plan Review Notes
Plan Review Notes For Permit 16021074
Permit Number 16021074
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-03-03 09:05:31FAIL
  
 1. PER NFPA 72 2010 EDITION 18.5.4.3.2 NOTIFICATION
 APPLIANCES MUST BE SYNCHRONIZED.
 2. PER NFPA 72 2010 EDITION 18.4.5.1 A MINIMUM OF 75
 DBA AT PILLOW TOP MUST BE ATTAINED IN ALL SLEEPING
 AREAS
 3. PER NFPA 101 FIFTH EDITION 31.3.4.3.5.1 LOCAL ALARMS
 MUST HAVE APPROVED SIGNAGE ABOVE EACH PULL STATION AND
 A MINIMUM OF ONE NOTIFICATION APPLIANCE ON THE EXTERIOR
 WALL OF THE BUILDING.
 4. PER NFPA 72 A HEAT OR SMOKE DETECTOR IS REQUIRED
 ABOVE THE FACP.