| Plan Review Notes For Permit 16021074 |
| Permit Number |
16021074 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-03 09:05:31 | FAIL | | | | | | 1. PER NFPA 72 2010 EDITION 18.5.4.3.2 NOTIFICATION | | | APPLIANCES MUST BE SYNCHRONIZED. | | | 2. PER NFPA 72 2010 EDITION 18.4.5.1 A MINIMUM OF 75 | | | DBA AT PILLOW TOP MUST BE ATTAINED IN ALL SLEEPING | | | AREAS | | | 3. PER NFPA 101 FIFTH EDITION 31.3.4.3.5.1 LOCAL ALARMS | | | MUST HAVE APPROVED SIGNAGE ABOVE EACH PULL STATION AND | | | A MINIMUM OF ONE NOTIFICATION APPLIANCE ON THE EXTERIOR | | | WALL OF THE BUILDING. | | | 4. PER NFPA 72 A HEAT OR SMOKE DETECTOR IS REQUIRED | | | ABOVE THE FACP. |
|