| Plan Review Notes For Permit 16021059 |
| Permit Number |
16021059 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-10 09:10:07 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16021059 | | | 3/10/16 | | | | | | 1) M1.1: IT IS NOT CLEAR HOW THE RETURN AIR SYSTEMS | | | WILL FUNCTION FOR HP-1 & 2 SUPPLYING THE STORAGE AREAS- | | | SEE WALL TYPE-1 DETAIL ON SHEET A-1: IT APPEARS BY THE | | | DETAIL THAT THE WHOLE STORAGE AREA AND THE INDIVIDUAL | | | STORAGE ROOMS WILL BE CLOSED OFF FROM FLOOR TO | | | UNDERSIDE OF ROOF DECK. HOW WILL THE AIR RETURN BACK TO | | | THE UNITS? | | | 2) M1.1: THE 8X6 TRANSFER DUCT IS UNDERSIZED PER | | | SECTION 601.5. | | | 3) M1.1: INDICATE THE WIDTH AND GAGE OF THE STRAP | | | HANGERS AND THE DIAMETER OF THE RODS SHOWN IN THE M1 | | | DETAIL, AND INDICATE THE TYPE AND SIZE OF FASTENERS FOR | | | ANCHORING TO THE STRUCTURE ABOVE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|